Diagnostics 41
787-2861 Electronic Circuit Breaker
Manual
Version 1.3.1
Pos: 71 /All e Seri en (Allgemei ne Module)/Ü berschriften/Ebene 1/Diagnose - Ü berschrift 1 @ 4\mod_1240831069471_21.docx @ 31372 @ 1 @ 1
8
Diagnostics
Pos: 72 /Serie 787 (EPSITRON)/F unkti onsbeschrei bung/Allgemeine Betriebszustände 787-2861 @ 23\mod_1436254565158_21.docx @ 185404 @ 2 @ 1
8.1
General Operating Statuses
Table 20: General Operating Statuses
Operating Status
Status LED
Level at
signal output S2
1
Push and slide switch
is pressed
Signal at
control input S1
Status 0:
Initialization of the device (boot
routine)
2
OFF
0 V
-
-
Status 1:
Channel switched ON.
Green
24 V
Status 4
Signal 3
→
Status 4
Status 2:
Channel switched ON.
Load current > 90% nominal
current
Green, flashing
(1 Hz)
24 V
Status 4
Signal 3
→
Status 4
Status 3:
Channel switched ON.
Load current > 100 % nominal
current
3
Green, flashing
(5 Hz)
24 V
Status 4
Signal 3
→
Status 4
Status 4:
Channel switched OFF manually
or through control input S1.
4
Red
24 V
Status 1
Signal 2
→
Status 1
Status 5:
Channel tripped.
Wait for temperature to return to
normal.
5
Red, flashing
(1 Hz)
0 V
-
-
Status 6:
Channel tripped.
Temperature returned to normal.
Channel can be switched ON
again.
6
Yellow flashing
0 V
Status 4
Signal 1
→
Status 1
Status 7:
Channel tripped.
Undervoltage with simultaneous
overcurrent.
Blue, flashing
(1 Hz)
0 V
Status 4
Signal 1
→
Status 1
Status 8:
Channel tripped.
Undervoltage
Blue, flickering
(1 Hz)
0 V
-
-
Status 9:
Channel tripped.
Overvoltage
Red, flickering
(1 Hz)
0 V
-
-
Status 10:
Device error, wiring error,
feedback voltage
Red/blue flickering
(1 Hz)
0 V
-
-
1
This status may differ for the 787-2861/0108-0020 device. More information is available in the “Signal Output S2 –
Indicators”.
2
The channel is activated again time delayed (170 ms … 500 ms) once the device initialization has concluded.
3
The channel is deactivated automatically in accordance with the given trip curve. The device then switches to Status 5.
4
The status is saved when the input voltage is switched OFF.
5
After a cooling (waiting) period, the channel switches to Status 6.
6
The channel can be re-activated as follows:
•
The push and slide switch is pressed twice or
•
a pulse (signal 1) is applied at the control input
(see section “Control Input S1”).
The device then switches to Status 1.
The following diagram “General Operating Statuses” visually displays the listed
operating statuses. However, not all operating statuses are shown.