765-1202/0100-0000
Properties
18
Product manual | Version: 1.0.0
16DIO FLD EC DC 24V 2.0A
4.4.2 Mechanical Data
Table 9: Mechanical Data
Property
Value
Width
60 mm
Height
30 mm
Length
210 mm
Weight
610 g
Housing
Zinc Die Casting
Mounting type
Screw mount, 2 × M4
Tightening torque
M4: 1.2 Nm
Mounting holes
Diameter: 4.5 mm
Distance from each: 198.0 mm ± 0.2 mm
4.4.3 Connection Technology
Table 10: Connection technology
Property
Value
Power Connection
PWR IN: M12 L-coded, 5-pin, plug
PWR OUT: M12 L-coded, 5-pin, socket
EtherCAT Connection
2 × M12, D-coded, socket, 4-pin
Digital inputs/outputs
8 × M12, A-coded, socket, 5-pin
Tightening Torque
M12: 1.0 Nm
Digital Input/Output, 1L or 2L Powered
Table 11: Digital Input/Output, 1L or 2L Powered
Property
Value
Digital Input
Characteristic
Type 3 (IEC 61131-2)
Parameters
Digital software input filter: without, 3 ms ... 20 ms
The input signal change must be at most 2.5 kHz for
correct device-internal detection of changes. However,
it should be noted that the transfer and processing of
the process data (in the device and in the controller)
also take time and reduce the maximum input signal
change.
Recording cycle
200 μs
Circuit
The digital input is not resistant to reverse power feed-
ing.
The input voltage must not exceed the supply voltage.
Indicators
On/off status LED
Digital Output
Output voltage
24 VDC
Port X01 to X04: 1L powered
Port X05 to X08: 2L powered
Current
Normal operation: max. 2.0 A per channel
Overload operation: max. 2.4 A per channel, per
IEC 61131-2
Residual current
Less than 1 mA