WAGO-I/O-SYSTEM 750
Appendix
97
750-451 8 AI RTD
Manual
Version 1.1.0
Table 73: Specific Module / Channel Parameters for 75x-451
GSD File
WAGO-I/O-
CHECK
Description
Value
Selection box
Value
Ni 1000 [TK 6180,
DIN 43760] HR
Ni 1000 [TK 5000, DIN
43760] HR
Pt 1000 [EN 60751] HR
Resistor 0R … 5K (linear)
Resistance
measurement 1
Resistor 0R … 1K2 (linear)
Resistance
measurement 2
Connection
type
deactivated
Connection type
deactivated
2-wire
*)
2-wire
*)
*)
Default setting
9.1.2.2 PROFIBUS DP (750-333, 750-833) Fieldbus Coupler
The aforementioned fieldbus couplers allow module-specific parameterization of
behavior at diagnosis.
Table 74: General Module / Channel Parameters
Parameter
Value
Explanation
Diagnosis
Channel x (x = 0…7)
The fieldbus coupler signals a diagnosis if the
I/O module reports the events:
•
Measuring range overflow
•
Measuring range underflow
•
Short circuit
•
Line break
0 (disabled)
*)
Diagnostics reported by the I/O module do not
lead to the signaling of a diagnosis by the
fieldbus coupler.
1 (enabled)
Diagnostics reported by the I/O module lead to
the signaling of a diagnosis by the fieldbus
coupler.
*)
Default setting