62
Commissioning
WAGO-I/O-SYSTEM 750
750-451 8 AI RTD
Manual
Version 1.1.0
7.1.1
Register Assignment
Table 46: Register 6
Register
Function
Memory
Access
Default setting
6
Diagnostics
RAM
R
–
Bit 0: Underrange
0
The resistance or temperature value calculated by the I/O module is above the lower
temperature/resistance limit.
1
The resistance or temperature value calculated by the I/O module is below the lower
temperature/resistance limit.
Bit 1: Overrange
0
The resistance or temperature value calculated by the I/O module is below the upper
temperature/resistance limit.
1
The resistance or temperature value calculated by the I/O module is above the upper
temperature/resistance limit.
Bit 2: User limiting value underrange
0
The resistance or temperature value calculated by the I/O module is above the lower
temperature/resistance limit parameterized by the user.
1
The resistance or temperature value calculated by the I/O module is below the lower
temperature/resistance limit parameterized by the user.
Bit 3: User limiting value overrange
0
The resistance or temperature value calculated by the I/O module is below the upper
temperature/resistance limit parameterized by the user.
1
The resistance or temperature value calculated by the I/O module is above the upper
temperature/resistance limit parameterized by the user.
Bit 4: Short circuit
0
”Indicate short circuit” is OFF or there is no short circuit.
1
”Indicate short circuit” is ON and there is a short circuit.
Bit 5: Wire break
0
”Indicate wire break” is OFF or there is no wire break.
1
”Indicate wire break” is ON and there is a wire break.
Bit 6: Group error
0
There is no error or bit 0, bit 1, bit 4 and/or bit 5 is/are not set.
1
General error
Bit 7 … 15: free