Pos: 17.2.1 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/Anwendung/AI/Anwendung 750- 04xx AI RT D par ametri erbar @ 10\mod_1313576749855_21.docx @ 77170 @ @ 1
The I/O module 750-451 (8 AI RTD) measures resistance at field level or
evaluates platinum or nickel resistance sensors.
The resistance values are converted into temperature values. A microprocessor in
the I/O module linearizes the measured resistance values and converts them into a
numeric value proportional to the temperature of the selected resistance sensor.
The
WAGO-I/O-
CHECK
commissioning tool can be used to set the required
operating mode.
Pos: 17.2.2 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/I/O-Beschrei bung/AI/I/O- Beschr eibung 750- 04xx 8 AI RTD Push-i n C AGE C LAM P @ 16\mod_1375368716345_21.docx @ 127583 @ @ 1
The I/O module has eight input channels, providing a direct connection to 2-wire
resistance sensors.
The sensors are connected to Push-in CAGE CLAMP
®
terA1/−A1 ...
+A8/−A8.
Pos: 17.2.3 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/I/O-Beschrei bung/Allgemein/Ver weis auf Kapi tel " Anschlüsse" @ 8\mod_1276775378035_21.docx @ 57956 @ @ 1
The assignment of the connections is described in the “Connectors” section.
Pos: 17.2.4 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/I/O-Beschrei bung/Allgemein/Ver weis auf Kapi tel " Geräte anschli eß en" > "Anschlussbeispi el(e)" @ 5\mod_1246015203281_21.docx @ 36298 @ @ 1
Connection examples are shown in section “Connecting Devices” > … >
“Connection Example(s)”.
Pos: 17.2.5 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/LED-Anzeige/LED Zustand Betrieb Kanal @ 5\mod_1245391732046_21.docx @ 35668 @ @ 1
The operating status of the channels is indicated by a green status LED per
channel.
Pos: 17.2.6 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/LED-Anzeige/LED Fehl er Kurzschluss/Drahtbruch/Bereichsüber-/unterschreitung @ 5\mod_1245391942765_21.docx @ 35672 @ @ 1
A red error LED per channel indicates a wire break, a short circuit or that the
signal is outside the measuring range.
Pos: 17.2.7 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/LED-Anzeige/Ver weis auf Kapitel "Anzeigeelemente" @ 5\mod_1246010525000_21.docx @ 36194 @ @ 1
The meaning of the LEDs is described in the “Display Elements” section.
Pos: 17.2.8 /Serie 750 (WAGO-I/O-SYST EM)/Wichtige Erläuterungen/Sicherheits- und sonstige Hinweise/Achtung/Achtung: M axi mal er Strom Leistungskontakte 10 A @ 3\mod_1226499143500_21.docx @ 25029 @ @ 1
Do not exceed maximum current via power jumper contacts!
The maximum current to flow through the power jumper contacts is 10 A.
Greater currents can damage the contacts.
When configuring your system, ensure that this current is not exceeded. If
exceeded, insert an additional supply module.
Pos: 17.2.9 /Serie 750 (WAGO-I/O-SYST EM)/Wichtige Erläuterungen/Sicherheits- und sonstige Hinweise/Hinweis/Hi nweis: Potenti alei nspeisekl emme für Erde einsetzen! ( kei ne LK für Erde) @ 3\mod_1226499037468_21.docx @ 25023 @ @ 1
Use supply modules for ground (earth)!
The I/O module has no power jumper contacts for receiving and transmitting the
earth potential. Use a supply module when an earth potential is needed for the
subsequent I/O modules.
Pos: 17.2.10 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Einl eitung/Versorgung/Anordnung unter Ber ücksichtigung der Leistungskontakte beliebig @ 3\mod_1233756233468_21.docx @ 27099 @ @ 1
With consideration of the power jumper contacts, the individual modules can be
arranged in any combination when configuring the fieldbus node. An arrangement
in groups within the group of potentials is not necessary.
Pos: 17.2.11 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Einl eitung/Einsatzbereich/Einsatzbereich 750- xxxx alle Koppler/C ontroll er ohne Ei nschränkung @ 3\mod_1232541691906_21.docx @ 26522 @ @ 1
The I/O module 750-451 can be used with all fieldbus couplers/controllers of the
WAGO-I/O-SYSTEM 750.
Pos: 17.3 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung/Ei nlei tung/Versorgung/Gal vanische Tr ennung F el d/System @ 3\mod_1233756478750_21.docx @ 27102 @ @ 1
The field voltage and the system voltage are electrically isolated from each other.
Pos: 17.4 /Dokumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1