50
Process Image
WAGO-I/O-SYSTEM 750
750-451 8 AI RTD
Manual
Version 1.1.0
4.3.12.2 S5-FB250 Format
With the setting “Pt1000 (IEC 751)” and activated S5-FB250 format, the I/O
module converts the measured resistance values of Pt1000 sensors (IEC 751) into
temperature values and outputs the conversion results.
The temperature values are displayed at a resolution of 1 digit per 0.05 °C.
The status information is depicted in bit 0 to bit 2 and the digitalized measured
value in bit 3 to bit 15.
Table 41: ID 10, Setting Pt1000 (IEC 751), S5-FB250 Format
Temperature
°C
Resistance
Ω
Numeric value
1)
with status information
4)
Status
byte
hex.
Error
LED
Binary
XFÜ
Hex.
Dec.
---
< 10.00
'1110.0000.1100.0 010'
0xE0C2
−7998
0x50
ON
Short circuit
2)
< −50.0
< 803.06
'1110.0000.1100.0 001'
0xE0C1
−7999
0x41
ON
Underrange
3)
−50.0
803.06
'1110.0000.1100.0 000'
0xE0C0
−8000
0x00
OFF
−25.0
901.92
'1111.0000.0110.0 000'
0xF060
−4000
0x00
OFF
0.0
1000.00 '0000.0000.0000.0 000'
0x0000
0
0x00
OFF
25.0
1097.35
0000.1111.1010.0 000'
0x0FA0
4000
0x00
OFF
50.0
1193.97 '0001.1111.0100.0 000'
0x1F40
8000
0x00
OFF
75.0
1289.87 '0010.1110.1110.0 000'
0x2EE0
12000
0x00
OFF
100.0
1385.06 '0011.1110.1000.0 000'
0x3E80
16000
0x00
OFF
125.0
1479.51 '0100.1110.0010.0 000'
0x4E20
20000
0x00
OFF
150.0
1573.25
0101.1101.1100.0 000'
5DC0
24000
0x00
OFF
> 150.0
> 1573.25
0101.1101.1100.0 001'
5DC1
24001
0x42
ON
Overrange
3)
---
> 5010.00
0101.1101.1100.0 010'
5DC2
24002
0x60
ON
Wire break
2)
1) Temperature values below 0 °C are represented in two's complement binary.
2) When short circuit and wire break monitoring is ON (see section “Diagnostics” > „Behavior in
the Event of an Error“)
3) When underrange / overrange limit is ON (see section “Diagnostics” > „Behavior in the Event
of an Error“)
4) Status information:
X: Not used,
F: Short circuit, wire break,
Ü: Underrange, overrange