150
•
EtherNet/IP (Ethernet/Industrial Protocol)
Object
model
WAGO-I/O-SYSTEM
750
ETHERNET TCP/IP
4.3.3.2.3 Explanations of the Object Description
Attribute ID:
Integer value which is assigned to the corresponded attribute
Access:
Set
The attribute can be accessed by means of Set_Attribute services.
Important: All the set attributes can also be accessed by means of
Get_Attribute services.
Get The attribute can be accessed by means of Get_Attribute services
NV:
NV (non volatile) The attribute is permanently stored in the coupler.
V (volatile)
The attribute is not permanently stored in the coupler.
Note: If this column is missing, all attributes have the type V
Name:
Designation of the attribute
Data type:
Designation of the CIP data type of the attribute
Description:
Short description for the Attribute
Default value:
Factory settings
4.3.3.2.4 Identity (01
hex
)
Class
Attribute
ID
Access Name
Data
type
Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Maximum Instance
0x0001
3
Get
Max ID Number
of Class
Attributes
UINT
Maximum number of Class
attributes
0x0000
4
Get
Max ID Number
of Instance
Attribute
UINT
Maximum number of instance
attributes
0x0000
Instance 1
Attribute
ID
Access
Name
Data type
Description
Default value
1
Get
Vendor ID
UINT
Manufacturer identification
40 (0x0028)
2 Get
Device Type
UINT
General type designation of
the product
12 (0x000C)
3
Get
Product Code
UINT
Designation of the coupler
e.g. 341 (0x0155)
Revision STRUCT
of:
Major Revision
USINT
4 Get
Minor Revision
USINT
Revision of the Identity
Objects
Depending on the
firmware