68 •
Fieldbus Coupler
Fieldbus Coupler 750-341
WAGO-I/O-SYSTEM
750
ETHERNET TCP/IP
3.1.8.1.1 System Group
The System Group contains general information to the coupler/controller.
Identifier
Entry
Ac-
cess
Description
1.3.6.1.2.1.1.1
sysDescr
R
This entry contains the device identification.
The entry is fix coded e. g. on
"WAGO 750-841".
1.3.6.1.2.1.1.2
sysObjectID
R
This entry contains the authorizing
identification of the manufacturer.
1.3.6.1.2.1.1.3
sysUpTime
R
This entry contains the time in hundredth
seconds since the last reset of the
managements unit.
1.3.6.1.2.1.1.4
sysContakt
R/W This entry contains the identification of the
contact person and contains information
about the contact possibilities.
1.3.6.1.2.1.1.5
sysName
R/W This entry contains an administrative name
for the device.
1.3.6.1.2.1.1.6 sysLocation R/W
This
entry contains the physical place of
installation of the node.
1.3.6.1.2.1.1.7
sysServices
R
This entry designates the quantity of services,
which this coupler/controller contains.
3.1.8.1.2 Interface Group
The interface Group contains information and statistics to the device interface.
Identifier
Entry
Ac-
cess
Description
1.3.6.1.2.1.2.1 ifNumber
R
Number
of network interfaces in the system
1.3.6.1.2.1.2.2
ifTable
-
Number of network interfaces
1.3.6.1.2.1.2.2.1
ifEntry
-
Entry network interface
1.3.6.1.2.1.2.2.1.1
ifIndex
R
This entry contains an unique assignment
number for each interface
1.3.6.1.2.1.2.2.1.2
ifDescr
R
This entry contains the name of the
manufacturer, the name of the product and
the version of the hardware Interface. E. g.
"WAGO Kontakttechnik GmbH 750-841:
Rev 1.0"
1.3.6.1.2.1.2.2.1.3
ifType
R
This entry describes the type of the
interface. Ethernet-CSMA/CD = 6,
Software-Loopback = 24
1.3.6.1.2.1.2.2.1.4
ifMtu
R
This entry specified the maximum transfer
unit (i.e. the maximum telegram length over
this interface to be transferred can).
1.3.6.1.2.1.2.2.1.5
ifSpeed
R
This entry indicates in bits the speed of the
interface.
1.3.6.1.2.1.2.2.1.6
ifPhysAddress
R
This entry indicates the physical address of
the interface. In the case of Ethernet this is
the MAC-ID.
1.3.6.1.2.1.2.2.1.7
ifAdminStatus
R/W This entry indicates the desired condition of
the interface. Possible values are here:
up(1) : Ready for use to sending and
receiving
down(2) : Interface is switched off