206
•
Process Data Architecture for EtherNet/IP
Specialty
Modules
WAGO-I/O-SYSTEM
750
ETHERNET TCP/IP
RTC Module
750-640
The RTC Module module has a total of 6 bytes of user data in both the Input
and Output Process Image (4 bytes of module data and 1 byte of control/status
and 1 byte ID for command). The following table illustrates the Input and
Output Process Image, which have 3 words mapped into each image. Word
alignment is applied.
Input and Output Process Image
Byte Destination
Instance
High Byte
Low Byte
Remark
ID
C/S
Command byte
Control/Status byte
D1 D0
n
D3 D2
Data bytes
The specialty modules represent 1x6 bytes input data and seize 1 Instance in
Class (0x67).and seize 1 Instance in Class (0x68).
DALI/DSI Master Module
750-641
The DALI/DSI Master module has a total of 6 bytes of user data in both the
Input and Output Process Image (5 bytes of module data and 1 byte of
control/status). The following tables illustrate the Input and Output Process
Image, which have 3 words mapped into each image. Word alignment is
applied.
Input Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0
D0
S
DALI Response
Status byte
1
D2
D1
Message 3
DALI Address
3
D4
D3
Message 1
Message 2
The specialty modules represent 1x6 bytes input data and seize 1 Instance in
Class (0x67).