210
•
Process Data Architecture for EtherNet/IP
System
Modules
WAGO-I/O-SYSTEM
750
ETHERNET TCP/IP
750-622
The Binary Space Modules 750-622 behave alternatively like 2 channel digital
input modules or output modules and occupy depending upon the selected
settings 1, 2, 3 or 4 bits per channel. According to this, 2, 4, 6 or 8 bits are
occupied then either in the process input or the process output image.
Input or Output Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
(Data bit
DI 8)
(Data bit
DI 7)
(Data bit
DI 6)
(Data bit
DI 5)
(Data bit
DI 4)
(Data bit
DI 3)
Data bit
DI 2
Data bit
DI 1
The Binary Space Modules seize 2, 4, 6 or 8 Instances in class (0x65) or in
class (0x66)..