Fieldbus
Communication
•
123
MODBUS
Functions
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
4.2.3.3 Function Code FC3 (Read multiple registers)
This function reads the contents of holding registers from a slave device in
word format.
Request
The request specifies the reference number (start register) and the word count
(register quantity) of the registers to be read. The reference number of the
request is zero based, therefore, the first register starts at address 0.
Example: Read registers 0 and 1:
Byte
Field name
Example
Byte 0, 1
Transaction identifier
0x0000
Byte 2, 3
protocol identifier
0x0000
Byte 4, 5
length field
0x0006
Byte 6
unit identifier
0x01 not used
Byte 7
MODBUS function code
0x03
Byte 8, 9
reference number
0x0000
Byte 10, 11 Word count
0x0002
Response
The reply register data is packed as 2 bytes per register. The first byte contains
the higher value bits, the second the lower values.
Byte
Field name
Example
.....
Byte 7
MODBUS function code
0x03
Byte 8
Byte count
0x04
Byte 9, 10
Value Register 0
0x1234
Byte 11, 12 Value Register 1
0x2345
The contents of register 0 are displayed by the value 0x1234 and the contents
of register 1 is 0x2345.
Exception
Byte
Field name
Example
.....
Byte 7
MODBUS function code
0x83
Byte 8
Exception code
0x01 or 0x02