194
•
Process Data Architecture for EtherNet/IP
Digital Output Modules
WAGO-I/O-SYSTEM
750
ETHERNET TCP/IP
Output Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
controls
DO 2
Channel 2
controls
DO 1
Channel 1
And the output modules seize 2 Instances in Class (0x66).
750-506, 753-506
The 750-506, 753-506 digital output module has 2-bits of diagnostic
information for each output channel. The 2-bit diagnostic information can
then be decoded to determine the exact fault condition of the module (i.e.,
overload, a short circuit, or a broken wire). The 4-bits of diagnostic data are
mapped into the Input Process Image, while the output control bits are in the
Output Process Image.
Input Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Diagnostic
bit S 3
Channel 2
Diagnostic
bit S 2
Channel 2
Diagnostic
bit S 1
Channel 1
Diagnostic
bit S 0
Channel 1
The output modules seize 4 Instances in Class (0x65).
Output Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
not used
not used
controls
DO 2
Channel 2
controls
DO 1
Channel 1
And the output modules seize 4 Instances in Class (0x66).
4 Channel Digital Output Modules
750-504, -516, -519, -531, 753-504, -516, -531, -540
Output Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
controls
DO 4
Channel 4
controls
DO 3
Channel 3
controls
DO 2
Channel 2
controls
DO 1
Channel 1
The output modules seize 4 Instances in Class (0x66).
4 Channel Digital Output Modules with Diagnostics and Input Process
Data
750-532
The 750-532 digital output modules have a diagnostic bit for each output
channel. When an output fault condition occurs (i.e., overload, short circuit, or