2857-570/024-001
Properties
Product manual | Version: 2.0.0
21
3-Phase Power Measurement Module, 1 A
Property
Value
Frequency range
•
Line frequency
•
Harmonic analysis
•
50 … 60 Hz
•
0 … 2665 Hz
Limit frequency
15,9 kHz
Signal form
Arbitrary periodic signals (with threshold frequen-
cies taken into account)
Test voltage
AC 3,51 kV, 50 … 60 Hz, 1 Min
2)
The following does not apply within the scope of UL: U
Lx–N
400 V / U
Lx–Ly
690 V under certain conditions; see
Special Requirements for Measurements with Higher Voltages outside the scope of UL [
Table 6: Technichal Data – Isolation type per EN/UL 61010-2-201 and EN/UL 61010-2-030
Property
Value
Measurement inputs / system
System Voltage U
LN
3)
≤ 300 V
Input requirement I
Lx
Current Transformer
Isolation type
Impedance and Supplementary Insulation
Overvoltage category
III
Measurement category
CAT III
Adjacent modules
System Voltage U
LN
3)
≤ 300 V
Isolation type
Impedance and Supplementary Insulation
Overvoltage category
III
3)
The system voltage is derived from the line-to-neutral voltage for common mains supply systems and is used
for determining insulation coordination.
See also
2
Special Requirements for Measurements with Higher Voltages outside the scope of
UL [
3.6.3 Special Requirements for Measurements with Higher Voltages outside the scope of
UL
Note
Above 300 V system voltage ratings are not permissable for UL!
Thus the following requirements for Measurements with Higher voltages without Voltage
Measurement Transformer (VT) are outside the scope of UL.
Measurements with higher voltages without VT are outside the scope of UL.
The following information applies to voltages U
Lx-N
400 VAC and U
Lx-Ly
to 690 VAC (see
8
Overview "Common Mains Supply Systems and Line Voltages" [
N port on the product is not used.
Table 7: Technical Data – Measurements with Higher Voltages, not permissable for UL
Property
Value
Nominal voltage
4)
• Phase voltage U
Lx−N
400 VAC
• Line-to-line voltage U
Lx−Ly
690 VAC