and the Output voltage of starter will be reduced gradually so that the Running
Speed of Motor can be cut down smoothly in case of the Mechanical Shock. The
Output Ending Voltage is the same as the initial Voltage. Soft-stopping Mode can
reduce or remove the Surge of the loading equipments such as the Water Pump.
You can set the Soft-stopping limit-current value through the FF item to reduce
the Big-current Shock to the Motor when stopping. This limit-current value is a
Percentage.
7.3.2 Free-stopping Mode (The F2 item is set as"0",this stopping mode is in use)
When using this mode to stop the motor, the Soft Starter will cut off the connection
to the By-pass Contactor and forbid the Controlled Silicon outputting voltage as
soon as receiving the order of stopping. The motor stops gradually because of its
Inertia. Generally, If the Soft-stopping Mode is not necessary, please choose the
Free-stopping mode to Length the service life of the soft starter. This mode
completely forbids the Instantaneous output, in case the instantaneous
big-current shock to the Motor in special application state.