The "Up" and "Down" ("
▲
""
▲
") key :In the Set Menu ,you can press these
two keys to choose the Function Code you need when the Colon is not shining
and can choose the Parameters under the Colon when Colon is shining ,It is the
same as the operation in Help Menu. When the Pass-by -lamp is lighting and the
Display Screen shows AXXX which means the operation current value of motor,
now you can press "Up" or "Down" key and the Screen will PXXXX or HXXXX i n t
u n (P X XXX means the apparent power of motor; HXXXX means the over-load
heat balance coefficient, if this value is more than 100%, the Screen shows
"Err06", that means it is at that state of over-load protection.)
Note:
1. only the operation is correct, it will be with the voice when pressing the
key. Otherwise, the operation is wrong.
● the control panel uses the super anti-interference material, so it can be state of
3 meters away.
5.2 Parameters set and explanation
The explanation for "Parameter-set "codes
Code
Explanation for
codes
The range
of value
Ex-factory
value
Special explanation
P0
This code is used
to set the “voltage
value”
30-70%
30%
This code can be used when the
starting mode is set as “Ramp
voltage to start,” and if is
“Limit-current” mode ,the value will
be fixed as 40%
P1
This code is used
to set the “soft
starting
2-60S
16S
It is invalid in“ Limit-Current”
starting mode.