4.2 The external terminal
Please see the diagram 4.2
●
Terminal
①
②
are by-pass output, are used to control the by-pass
contactor. They are normal open contacts and are closed when finishing starting.
The contact capacity is Ac250V/5A
●
Terminal
③ ④
are programmable relay output: it is set by FJ code .They
are normal open no-power contacts Please see the detailed information in 5.3
item. The contact capacity is AC250V/5A
●
Terminal
⑤
⑥
are fault output , they will be closed when there are any
fault matters happened to the soft starter or loose electricity, while at normal case
they are open. The contact Capacity is AC25V/0.3A
●
Terminal
⑦
are Instantaneous stop input, this terminal must be connected
with terminal
⑩
when the starter works normally. But if these two terminals are
both open, the soft starter will stop, and at this time the starter is at the state of
fault protection. Terminal
⑦
can be controlled by the output contact of external
protection dives, and it is useless when the F12Key is set as 0(basic protection).
●
Terminal
⑧ ⑨ ⑩
are start-up or stop input .There two ways of connections
for your choose, those are 3-wire connection and 2-wire connection.
●
Please see the diagram 4.3