VSI Series 1000-X Electric Actuator

Operation and Maintenance Manual

9

APPLICATION REQUIREMENTS

 Series 1000-X units may be installed in indoor or 

outdoor conditions up to IP67 or NEMA 4X

Series 1000-X units are not rated for hazardous 

environments and caution should be taken to avoid 

flammable and explosive environments.

WARNING

• Manual override operation and maintenance tasks 

should be taken into consideration when installing 

units.

• Ambient temperature should be within -22°F to 

+140°F. 

Installation Conditions

•  Care should be taken to prevent the heat of the 

working medium from raising the actuator above 

its rated ambient temperature limits.

• When the temperature of the working medium 

exceeds the actuator’s rated temperature limits, a 

thermal coupling shall be installed to reduce heat 

transfer between the medium and the actuator.

Medium temperatures above 175°F require the use of 

bracket and thermal isolating coupling in lieu of direct 

mounting to valve.

WARNING

Medium/Radiant Heat

• Refer to Figure 1.1 and 1.2 when connecting 

conduit to Series 1000-X actuators.

• Conduit entries are ½” NPT.  All entry fittings 

should be sealed watertight.

•  Best practice when connecting conduit to Series 

1000-X actuators is to run the conduit from below 

the actuator upward to prevent condensation from 

conduit working into the actuator; as shown in 

Figure 1.2.

Conduit and Cable Installation

•  If actuator must be installed below conduit, a drip 

loop or drain should be provided to allow any water 

to exit the piping.

Conduit and Cable Installation (Cont.)

Waterproof

cable connector

Branch

Connector

Plastic tube

Seal Ring

Cable

Lock Nut

ø9 ~ ø11

Figure 1.1

Figure 1.2

•  Refer to Figure 2 for installation of cable directly 

into unit without the use of conduit.

•  The outer diameter of the cable shall be Ø9mm- 

Ø11mm.

• Use of cable smaller than specified may allow 

water to enter the unit and damage the electronics.

• When possible, power wiring and signal wiring 

should be routed through separate conduit entries; 

all units have two conduit entries.

Figure 2

Summary of Contents for 1000-X Series

Page 1: ...ANCE MANUAL VER0815 2 For information on this product and other VSI products please visit our web page www valvesolutions com COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION OPEN CLOSE SERVICE ELECTRI...

Page 2: ...wiring should follow these diagrams Do not manually operate the actuator without deenergizing actuator with factory installed push button or by external disconnect such as a circuit breaker NOTICE Va...

Page 3: ...ar Group 4 Front Wiring Cover 14 Capacitor 5 Push Button 15 Open Cam Lock Screw 6 Conduit Plugs 16 Close Cam Lock Screw 7 Hex Handle 17 Position Indicator 8 Hex Handle Bracket 18 SPDT Limit Switches 9...

Page 4: ...220 VAC Motor Power 10W Rated Current 1 7A 0 24A 0 16A Max Current 1 9A 0 34A 0 17A Standard Torque 443inlb 50NM Run Time 1005 X 17 0 5 sec 1005 XL 21 0 5 sec Turning Angle 90 Adjustable 5 Total Weigh...

Page 5: ...Max Current 2 40A 0 81A 0 52A Standard Torque 885inlb 100NM Run Time 24 5 0 5 sec Turning Angle 90 Adjustable 5 Total Weight 9 10lbs 4 13kg Insulating Resistance 100M 250VDC 100M 500VDC Overvoltage Wi...

Page 6: ...8A 3 41A 3 60A Total Weight 19 4lbs 8 80kg 20 9lbs 9 46kg 20 9lbs 9 463kg 220VAC Motor Power 40W 90W 90W Rated Current 0 37A 0 57A 0 60A Max Current 0 78A 1 78A 1 87A Total Weight 19 7lbs 8 91kg 21 2l...

Page 7: ...tor Power 140W 140W 140W Rated Current 0 94A 0 98A 0 98A Max Current 2 12A 2 20A 2 20A Total Weight 41 2lbs 18 7kg 41 9lbs 19 0kg 42 4lbs 19 2kg Standard Torque 8 850inlb 1 000NM 14 160inlb 1 600NM 22...

Page 8: ...ltage DC Voltage 1005 X and 1005 XL 3A 250VAC NR 1010 X thru 1250 X 15A 250VAC 0 6A 125VDC 1 Power Common 2 Close Operation Power Hot 3 Open Operation Power Hot 4 Auxiliary Contact Common 5 Auxiliary...

Page 9: ...ating coupling in lieu of direct mounting to valve WARNING Medium Radiant Heat Refer to Figure 1 1 and 1 2 when connecting conduit to Series 1000 X actuators Conduit entries are NPT All entry fittings...

Page 10: ...Attach the bracket with proper bolts and tighten all bolts If bolt holes are not aligned but within Installation of Actuator to Valve 5 alignment rotate actuator handwheel to move actuator into alignm...

Page 11: ...e plate Dome indication Full open position Full close position Lock screw Opening gear Shut position regulating shaft Openpositionregulatingshaft S Red O Green D2 D1 O S K1 K2 K3 K4 Open direction mid...

Page 12: ...ltage The actuator is in thermal protection mode due to over torque situation or ambient temperature is too high Remove over torque conditions Check valve to ensure manual movement without sticking Co...

Reviews: