background image

VSI Series 1000-X Electric Actuator

Operation and Maintenance Manual

5

Direct Mount Parameters

Square Shaft

Mounting Flanges

Stem Height

17 x 17

F05

F07

Height 

 32mm

126

71

55

24

95.5

196

100.5

129

S

O

Ø70
Ø50

4-M8

4-M6

45

°

Evenly Distributed

Evenly Distributed

Ø90

32

33

S

O

Fig. A

1010-X SPECIFICATIONS

Power Supply

24 VAC

110 VAC

220 VAC

Motor Power

25W

Rated Current

2.11A

0.57A

0.35A

Max. Current

2.40A

0.81A

0.52A

Standard Torque

885inlb/100NM

Run Time

24.5 ± 0.5 sec

Turning Angle

90° Adjustable ± 5°

Total Weight*

9.10lbs/4.13kg

Insulating Resistance

100M

Ω

/250VDC

100M

Ω

/500VDC

Overvoltage Withstanding

500VAC - 60 sec

1500VAC - 60 sec

Protection Class

IP67  NEMA 4X

Installation Angle

At or above the centerline of pipe. See Fig. A

Ambient Temperature

-22°F to +140°F (-30°C to +60°C)

Ambient Humidity

 95% Relative Humidity

Duty Cycle

80%

Options

Handwheel Override, Motor Pushbutton

X

*Weight may vary with selected options

NA on 24VAC Units

OVERALL DIMENSIONS AND SPECIFICATIONS FOR 1010-X

Summary of Contents for 1000-X Series

Page 1: ...ANCE MANUAL VER0815 2 For information on this product and other VSI products please visit our web page www valvesolutions com COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION OPEN CLOSE SERVICE ELECTRI...

Page 2: ...wiring should follow these diagrams Do not manually operate the actuator without deenergizing actuator with factory installed push button or by external disconnect such as a circuit breaker NOTICE Va...

Page 3: ...ar Group 4 Front Wiring Cover 14 Capacitor 5 Push Button 15 Open Cam Lock Screw 6 Conduit Plugs 16 Close Cam Lock Screw 7 Hex Handle 17 Position Indicator 8 Hex Handle Bracket 18 SPDT Limit Switches 9...

Page 4: ...220 VAC Motor Power 10W Rated Current 1 7A 0 24A 0 16A Max Current 1 9A 0 34A 0 17A Standard Torque 443inlb 50NM Run Time 1005 X 17 0 5 sec 1005 XL 21 0 5 sec Turning Angle 90 Adjustable 5 Total Weigh...

Page 5: ...Max Current 2 40A 0 81A 0 52A Standard Torque 885inlb 100NM Run Time 24 5 0 5 sec Turning Angle 90 Adjustable 5 Total Weight 9 10lbs 4 13kg Insulating Resistance 100M 250VDC 100M 500VDC Overvoltage Wi...

Page 6: ...8A 3 41A 3 60A Total Weight 19 4lbs 8 80kg 20 9lbs 9 46kg 20 9lbs 9 463kg 220VAC Motor Power 40W 90W 90W Rated Current 0 37A 0 57A 0 60A Max Current 0 78A 1 78A 1 87A Total Weight 19 7lbs 8 91kg 21 2l...

Page 7: ...tor Power 140W 140W 140W Rated Current 0 94A 0 98A 0 98A Max Current 2 12A 2 20A 2 20A Total Weight 41 2lbs 18 7kg 41 9lbs 19 0kg 42 4lbs 19 2kg Standard Torque 8 850inlb 1 000NM 14 160inlb 1 600NM 22...

Page 8: ...ltage DC Voltage 1005 X and 1005 XL 3A 250VAC NR 1010 X thru 1250 X 15A 250VAC 0 6A 125VDC 1 Power Common 2 Close Operation Power Hot 3 Open Operation Power Hot 4 Auxiliary Contact Common 5 Auxiliary...

Page 9: ...ating coupling in lieu of direct mounting to valve WARNING Medium Radiant Heat Refer to Figure 1 1 and 1 2 when connecting conduit to Series 1000 X actuators Conduit entries are NPT All entry fittings...

Page 10: ...Attach the bracket with proper bolts and tighten all bolts If bolt holes are not aligned but within Installation of Actuator to Valve 5 alignment rotate actuator handwheel to move actuator into alignm...

Page 11: ...e plate Dome indication Full open position Full close position Lock screw Opening gear Shut position regulating shaft Openpositionregulatingshaft S Red O Green D2 D1 O S K1 K2 K3 K4 Open direction mid...

Page 12: ...ltage The actuator is in thermal protection mode due to over torque situation or ambient temperature is too high Remove over torque conditions Check valve to ensure manual movement without sticking Co...

Reviews: