“Speed Adjustment Menu” page
Select "Speed" from the Installer “Use menu" to access the speed adjustment menu.
Motor speed can be adjusted depending on the system flow rates, selecting:
[
▲
]
[
▲
]
035
VSUP1
VSUP2
VSUP3
VSUPB
VEXHB
VEXH1
VEXH2
VEXH3
[
▲
]
SPEED
[
▲
]
ENGLISH
“Alarms” page
Access the "Alarm" page only if the machine detects one of the problems detailed below:
• Alarm: Supply air temperature <5°C
occurs with machine block (manual reset).
• Alarm: No Frost - Wait an hour
occurs with machine block (manual reset).
• Alarm : Ext Probe fault
occurs without blocking the machine (No Frost, Bypass: deactivated).
• Alarm : Int Probe fault
occurs without blocking the machine. (“By-pass”: deactivated).
• Alarm : Exh Probe fault
occurs without blocking the machine. (No Frost: deactivated).
Alarm with machine block: the messages "Alarm!" and "Block!" appear alternately on the "HOME" page.
Alarm without blocking the machine: on the “HOME” page, the message “Alarm!” Appears.
In the presence of alarms: select the "ALARM" line on the "MAIN MENU" page and press the [
] key.
The dialogue window opens with the instructions on how to resolve the problem.
Warning:
After 2 minutes with no keys being pressed, the display returns to the "Home" page without saving any changes.
!
MAIN MENU
USE MENU
ALARM
SETUP
INFO
VSUP1
= Clean air outlet inside the room (minimum speed ‘1’)
VEXH1
= Stale air outlet to outside.
VSUP2
= Clean air outlet inside the room (speed ‘2’)
VEXH2
= Stale air outlet to outside.
VSUP3
= Clean air outlet inside the room (speed ‘3’)
VEXH3
= Stale air outlet to outside.
VSUPB
= Clean air outlet inside the room (maximum speed - ‘Boost’)
VEXHB
= Stale air outlet to outside.
Clean air outlet inside the room: see A fig. 2 / Stale air outlet to outside: see D fig.2.
[
▲
]
[
▲
]
[
]