33
ENGLISH
MAIN MENU
USE MENU
ALARM
SETUP
INFO
PASSWORD
023
TECHNIC.
SETP BYP.
LIFE TIME
RESET FIL
MBUS ID
SPEED
LANGUAGE
NO FROST
QUIET
QUIET PR.
Installer "Operations menu" page
Enter the password as shown in the figure to access the installer "Operations menu."
From this new page you can manage:
•
Setp Byp.
“By-pass” function activation depends on the “Setp Byp”
temperature. “Setp Byp” is selectable into a variable range
between: 15°C & 30°C (default value = 18°C).
•
Lifetime
Is shown the duration of Filters Pre-Alarm.
(See “Pre -alarm: Filters checking”):
- after 3 or 6 or 12 months;
•
Reset Fil
In case of Filters replacing, you need to reset the Filters Timer
manually:
- select [YES] to reset;
- select [NO] to not resect.
•
Modbus ID
In the presence of another HMI user interface installed in
remote, you can configure an address other than that set by
default which is "160" (for code 12106) or "1" (for code
12107). (page 39)
•
Speed
See Fig. 3
From “Installer menu” page, selecting “Speed”, you can join to
“Setting speed”. Here, you can set motorfan speeds:
(C)
Clean air outlet inside the room;
(D)
Stale air outlet to outside.
For more details on setting “Speed”, See:
“Setting Speed Menu”
[
▲
]
[
▲
]
018
SETP BYP.
[
▲
]
[
▲
]
003
LIFE TIME
[
▲
]
[
▲
]
YES
RESET FIL
[
▲
]
[
▲
]
160
MODBUS ID
VSUP3
VEXH3
VSUP B
VEXH B
VSUP1
VEXH1
[
▲
]
[
▲
]
VSUP2
VEXH2
SPEED