background image

11

terminal must be protected by a guard of durable material. The
guard must be fitted centrally over the terminal.  Refer to I.S. 813,
when the terminal is 0.5 metres (or less) below plastic guttering
or 1 metre (or less) below painted eaves.

3A.5 AIR SUPPLY

The following notes are intended for general guidance only.
This appliance is a room-sealed, fan-flued boiler, consequently
it does not require a permanent air vent for combustion air
supply.
When installed in a cupboard or compartment, ventilation for
cooling purposes is also not required.

3A.6 WATER CIRCULATION

Specific recommendations are given in I.S. 813.  The following
notes are for general guidance only.

3A.6.1 PIPEWORK

It is recommended that copper tubing be used in conjunction
with soldered capillary joints.
Where possible pipes should have a gradient to ensure air is
carried naturally to air release points and that water flows
naturally to drain cocks.
Except where providing useful heat, pipes should be insulated
to avoid heat loss and in particular to avoid the possibility of
freezing. Particular attention should be paid to pipes passing
through ventilated areas such as under floors, loft space and
void areas.

3A.6.2 AUTOMATIC BY-PASS

The appliance has a built-in automatic by-pass, consequently
there is no requirement for an external by-pass, however the
design of the system should be such that it prevents boiler
‘cycling’.

3A.6.3 DRAIN COCKS

These must be located in accessible positions to facilitate
draining of the appliance and all water pipes connected to the
appliance.

3A.6.4 AIR RELEASE POINTS

These must be positioned at the highest points in the system
where air is likely to be trapped. They should be used to expel
trapped air and allow complete filling of the system.

3A.6.5 EXPANSION VESSEL

The appliance has an integral expansion vessel to
accommodate the increased volume of water when the system
is heated. It can accept up to 8 litres of expansion from within
the system, generally this is sufficient, however if the system
has an unusually high water content, it may be necessary to
provide additional expansion capacity (see 6.18).

3A.6.6 FILLING POINT

A method for initial filling of the system and replacing water lost
during servicing etc. is provided (see fig. 7). You should ensure
this method of filling complies with the local water authority
regulations.

3A.6.7 LOW PRESSURE SEALED SYSTEM

An alternative method of filling the system would be from an
independent make-up vessel or tank mounted in a position at
least 1 metre above the highest point in the system and at least
5 metres above the boiler (see fig. 8). The cold feed from the
make-up vessel or tank must be fitted with an approved non-
return valve and stopcock for isolation purposes. The feed pipe
should be connected to the return pipe as close to the boiler as
possible.

3A.6.8 FREQUENT FILLING

Frequent filling or venting of the system may be indicative of a
leak. Care should be taken during the installation of the
appliance to ensure all aspects of the system are capable of
withstanding pressures up to at least 3 bar.

3A.7 ELECTRICAL SUPPLY

The appliance is supplied for operation on 230V @ 50Hz
electrical supply; it must be protected with a 3-amp fuse. The
method of connection to the mains electricity supply must allow
for complete isolation from the supply. The preferred method
is by using a double-pole switch with a contact separation of at
least 3,5 mm (3° high-voltage category). The switch must only
supply the appliance and its corresponding controls, i.e. time
clock, room thermostat, etc.

3A.8 MOUNTING ON A COMBUSTIBLE
SURFACE

If the appliance is to be fitted on a wall of combustible material,
a sheet of fireproof material must protect the wall.

3A.9 TIMBER FRAMED BUILDINGS

If the appliance is to be fitted in a timber framed building, it
should be fitted in accordance with I.S. 813 and local Building
Regulations.
The Institute of Gas Engineers publication (IGE/UP/7) ‘Guide
for Gas Installations in Timber Frame Buildings’ gives specific
advice on this type of installation.

3A.10 INHIBITORS

Vokèra recommend that an inhibitor - suitable for use with
copper heat exchangers - is used to protect the boiler and
system from the effects of corrosion and/or electrolytic action.
The inhibitor must be administered in strict accordance with the
manufacturers instructions*.
*Water treatment of the complete heating system - including the
boiler - should be carried out in accordance with I.S. 813 and
the Domestic Water Treatment Association’s (DWTA) code of
practice.

3A.11 SHOWERS

If the appliance is intended for use with a shower, the shower
must be thermostatically controlled and be suitable for use
with a combination boiler.

3A.12 DECLARATION OF CONFORMITY

A Declaration of Conformity (as defined in I.S. 813) must be
provided on completion of the installation.
A copy of the declaration must be given to the responsible
person and also to the gas supplier if required.

Summary of Contents for Compact 24 SE

Page 1: ...INSTRUCTIONS TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK C...

Page 2: ...4 Flue system 10 3A 5 Air supply 11 3A 6 Water circulation 11 3A 7 Electrical supply 11 3A 8 Mounting on a combustible surface 11 3A 9 Timber framed buildings 11 3A 10 Inhibitors 11 3A 11 Showers 11...

Page 3: ...r Vok ra Compact SE boiler has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and efficiency Please there...

Page 4: ...ounter clockwise to reduce the temperature range 37 C 60 C Boiler at OFF standby Select this position when you want the boiler to be switched off for short periods days or if the boiler requires to be...

Page 5: ...ppliance fails to ignite during the ignition sequence it will enter a lockout condition Should this occur please allow a period of at least two minutes before re setting the appliance 2 6 EXPLANATION...

Page 6: ...f you think your boiler may have developed a fault please contact your installer or Vok ra Customer Services 0844 3910999 UK or 056 7755057 ROI have all your details to hand including full address and...

Page 7: ...a sealed system only consequently they are not intended for use on open vented systems This booklet is an integral part of the appliance It is therefore necessary to ensure that the booklet is handed...

Page 8: ...e minute anti cycle timer delay When the request for heat has been satisfied the appliance pump and fan may continue to operate to dissipate any residual heat within the appliance 1 4 MODE OF OPERATIO...

Page 9: ...ht mm 715 Width mm 405 Depth mm 248 Dry weight kg 28 2 6 Clearances Compact 24 SE Sides 12mm Top 150mm from casing or 25mm above flue elbow whichever is applicable Bottom 150mm Front 500mm 2 7 Connect...

Page 10: ...from a terminal on the same wall 300 mm P From a structure to the side of the vertical terminal 300 mm Q From the top of the vertical terminal to the roof flashing As determined by the fixed collar of...

Page 11: ...to which BS 5440 PART 1 FLUES BS 5440 PART 2 FLUES VENTILATION BS 5449 PART 1 FORCED CIRCULATION HOT WATER SYSTEMS BS 5546 INSTALLATION OF GAS HOT WATER SUPPLIES FOR DOMESTIC PURPOSES BS 6798 INSTALLA...

Page 12: ...1363 is acceptable 3 8 MOUNTING ON A COMBUSTIBLE SURFACE If the appliance is to be fitted on a wall of combustible material a sheet of fireproof material must protect the wall 3 9 TIMBER FRAMED BUILD...

Page 13: ...SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a position at least 1 metre above the highest point in the system and at least...

Page 14: ...flue applications to be considered alternatively the Vok ra twin flue system can be utilised if longer flue runs are required 4 5 2 CONCENTRIC HORIZONTAL FLUE For concentric vertical flue see 4 5 2 Fo...

Page 15: ...ion of the 90 bend Fig 12 Total flue length 60 100 Restrictor required Up to 1 85 metre 42 mm diameter From 1 85 to 3 35 metre 44 mm diameter From 3 35 to 5 25 metre Not installed NOTE These instructi...

Page 16: ...rough the ceiling and or roof Depending on site conditions it may be preferable to install the terminal assembly prior to fitting the twin flue pipes Fit the appropriate flashing plate to the roof and...

Page 17: ...2mm pipe to the inlet of each valve and tighten both nuts NOTE Depending on system requirements it may necessary to increase the size of the flow return pipe work after the service valve connections 4...

Page 18: ...ed as outlined below locate and unscrew the 2 screws A that secure the outer casing to the appliance lift the casing upward to disengage it from the top locating hooks and then remove store the casing...

Page 19: ...e gas rate then a combustion analysis test must be carried out in accordance with BS 7967 UK to ensure the appliance is left working safely and correctly Additionally if the gas valve has been adjuste...

Page 20: ...these instructions and explain the importance of keeping them in a safe place Explain to the user how to isolate the appliance from the gas water and electricity supplies and the locations of all drai...

Page 21: ...cking pin I from the pump assembly and remove the AAV assembly J Replace in the reverse order 6 8 WATER PRESSURE SWITCH fig 24 Carry out component removal procedure as described in 6 4 Locate and remo...

Page 22: ...the inner combustion cover and remove Disconnect the spark plug cable connection slide off the lower cable grommet from the seat of the air distribution box remove the burner fixing screws and remove...

Page 23: ...t the cold water inlet pipe at the DHW flow switch B2 Using a small screwdriver gently ease the flow restrictor C2 from its seating Replace in the reverse order Ensure all seals are in good condition...

Page 24: ...minutes timer delay When a new ignition sequence begins the output of the appliance is set at minimum for two minutes NOTE Any demand for hot water has the priority If there is a demand for hot water...

Page 25: ...umper JP2 turn the domestic hot water temperature adjustment knob C until it reaches the heating maximum value as indicated in the multigas table remove the jumper JP2 to store the heating maximum val...

Page 26: ...sing cycle the temperature value is restored to the value set by the user and the above mentioned cycle is repeated until the ambient thermostat request is fulfilled Fixed green if there is flame the...

Page 27: ...uminated See table on page 4 7 7 5 RESISTANCE TO EARTH CHECK Isolate the appliance from the electrical supply and using a suitable multi meter carry out a resistance test Connect test leads between th...

Page 28: ...4 VOK RA LOWER COVER MECHANICAL CLOCK fig 3 The Vok ra lower cover mechanical clock kit product code 20025081 is entirely suitable for the Compact 24SE and eliminates the need for an external time co...

Page 29: ...d LED Led 1 green working status or temporary stop Led 2 Not installed Led 3 red boiler lock out F1 Fuse 2A T F External fuse 3 15A F M3 Terminal strip for electrical connection hight power P Pump OPE...

Page 30: ...circuit board MP08 20005569 21 Led light guide 20013352 26 Control panel 20035608 27 Knob 20013055 31 Case Assembly 20026073 34 Fixing flange 20023928 90 Fuse R3478 470 Ignition transformer TR6 R1002...

Page 31: ...w actuator R10022349 27 Heating cock R1789 28 Connection R1790 30 Water supply stop cock R7099 36 Pipe 20005557 48 Cock 20000533 63 Pipe 20035609 201 Washer R5026 265 Washer R5236 266 Washer R5237 288...

Page 32: ...20029826 2 Pipe R10028603 3 Pump R10027571 4 Air vent bottle R10025485 7 Pipe 20005559 8 Heat exchanger 20005544 9 Pipe 20005558 200 Washer R5023 290 Clip R2165 299 Washer R10022726 302 Washer R5025...

Page 33: ...551 5 Spark ignition electrode R10025985 12 Gas pipe 20005554 13 Gas valve 20035533 14 Gas pipe 20005553 15 3 4 gas cock R10020897 16 Combustion chamber cover 20005594 17 Gas valve solenoid R10020838...

Page 34: ...ation panel 20005560 7 Flue draught diverter 20005596 10 Fan kit 20026724 11 Pressure connection 20021548 12 Fumes connection 20011048 13 Segnal amplifier 20025687 17 Washer 20005552 22 Flange 42 R100...

Page 35: ...ution box over and combustion chamber cover fig 22 disconnect the spark plug cable connection slide off the lower cable grommet from the seat of the air distribution box remove the burner fixing screw...

Page 36: ...ALL INSTALLATIONS If required by the manufacturer record the following CO2 OR CO ppm OR CO CO 2 Ratio The heating and hot water system complies with the appropriate Building Regulations Yes The boile...

Page 37: ...ignature SERVICE 7 Date Energy Efficiency Checklist completed Yes No Engineer Name Company Name Telephone Number CORGI ID Number Comments Signature SERVICE 9 Date Energy Efficiency Checklist completed...

Page 38: ......

Page 39: ......

Page 40: ...s vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve the...

Reviews: