background image

24

7.4 COMBUSTION ANALYSIS TEST

To carry out the combustion analysis, proceed as follows:
- open the hot water tap to its maximum output
- set the mode selector to summer and the domestic hot water

temperature selector to the maximum value

- remove the screw of the combustion analysis inlet cover

and insert the probes

- power the boiler

The appliance works at maximum output and it is possible to
check combustion.

After analysis is complete:
- close the hot water tap
- remove the probe from the analyser and close the

combustion analysis inlet fastening carefully the screw
previously removed.

7.5 CHECKING THE EXPANSION VESSEL

Carry out the component removal procedure as described in
6.4. You must ensure that the boiler is completely drained of
water. Using a suitable pressure gauge, remove dust cap on
expansion vessel and check the charge pressure.  The correct
charge pressure should be 1.0 bar ± 0.1 bar. If the charge
pressure is less, use a suitable pump to increase the charge.

NOTE

You must ensure the drain valve is in the open position whilst
re-charging takes place. Replace the dust cap and carry out the
relevant commissioning procedure (section 5).

7.6 EXTERNAL FAULTS

4.4 Light signals and faults

The control panel has two led that indicate the boiler operating
status:

Green led
Flashing

- Flashing with frequency 0.5 second on - 3.5 seconds off =

boiler in standby, there is no flame.

- Flashing with frequency 0.5 second on - 0.5 second off =

temporary stop of the appliance due to the following self-
restoring faults:
- water pressure switch (standby time 10 minutes
approximately)
- differential air pressure switch (standby time 10 minutes
approximately)
- transitory waiting for ignition.

In this phase, the boiler waits for restoration of working
conditions. If after standby time, the boiler will not restore regular
operation, stop will be permanent and light signalling will be
red.
- Fast flashing (frequency 0.1 sec. on; 0.1 sec. off; duration

0.5) input/output function S.A.R.A. (Italian acronym for
Environment Automatic Adjustment System)
By setting the heating water temperature selector to the
area marked by AUTO - temperature value from 55 to 65°C
- the S.A.R.A. self-adjusting system is activated: the boiler
varies the delivery temperature according to the closing
signal of the ambient thermostat. When the temperature set
with the heating water temperature selector is reached, a
20 minutes count begins. If during this period the ambient
thermostat still requests heat, the value of the set tempera-
ture automatically increases by 5°C.
When the new value is reached, other 20 minutes count
begins.
If during this period the ambient thermostat still requests
heat, the value of the set temperature automatically
increases by 5°C.
This new temperature value is the result of the temperature
set manually with the heating water temperature selector
and the increase of +10°C of the S.A.R.A function.
After the second increasing cycle, the temperature value is
restored to the value set by the user and the above
mentioned cycle is repeated until the ambient thermostat
request is fulfilled.

Fixed green

if there is flame, the boiler works regularly.

Red led

The red led indicates a boiler lockout due to the following
faults:

Fixed

- flame lockout
- air pressure switch intervention (after transient phase)
- NTC heating probe
- ACF electronic fault alarms

Flashing

- limit thermostat intervention
To reset operation, place the mode selector on OFF/stand-by,
wait 5-6 seconds and take it then to the desired position:
summer or winter mode.
If the boiler does not restore normal operation, contact the
Technical Assistance Service.

Green flashing led + red flashing led

When the LEDs flash 

simultaneously 

it is a domestic water

probe alarm and water pressure switch alarm (after transient
phase). The boiler works regularly, but stability of the domestic
hot water temperature is not guaranteed.
Contact the Technical Assistance Service for a control.
When the LEDs flash 

alternatively 

it means that there is a

calibration procedure in progress.

7.7 ELECTRICAL CHECKS

Any electrical checks must be carried out by a suitably qualified
person.

7.7.1 EARTH CONTINUITY TEST

Isolate the appliance from the electrical supply, and using a
suitable multi-meter carry out a resistance test. Connect test
leads between an appliance earth point and the earth wire of
the appliance supply cable. The resistance should be less than
1 OHM. If the resistance is greater than 1 OHM check all earth
wires and connectors for continuity and integrity.

7.7.2 SHORT CIRCUIT CHECK

Isolate the appliance from the electrical supply, and using a
suitable multi-meter, carry out a short circuit test between the
Live & Neutral connections at the appliance terminal strip.
Repeat above test on the Live & Earth connections at the
appliance terminal strip.

NOTE

Should it be found that the fuse has failed but no fault is
indicated, a detailed continuity check will be required to trace
the fault. A visual inspection of components may also assist in
locating the fault.

7.7.3 POLARITY CHECK

With the appliance connected to the electrical supply and
using a suitable multimeter, carry out the following voltage
tests:

connect test leads between the Live & Neutral connections
at the appliance terminal strip. The meter should read
approximately 230V ac. If so proceed to next stage. If not, see
7.7.4.

connect test leads between the Live & Earth connections at
the appliance terminal strip. The meter should read
approximately 230V ac. If so proceed to next stage. If not, see
7.7.4.

connect test leads between the Neutral & Earth connections
at the appliance terminal strip. The meter should read
approximately 0 – 15Vac. If so polarity is correct. If not, see
7.7.4.

7.7.4 REVERSED POLARITY OR SUPPLY FAULT

Repeat the above tests at the appliance isolator, if testing
reveals correct polarity and/or supply at the isolator, re-check
wiring and connections between the isolator and the appliance.
If tests on the isolator also reveal reversed polarity or a supply
fault, consult the local electricity supplier for advice.

Summary of Contents for Compact 24 SE

Page 1: ...INSTRUCTIONS TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK C...

Page 2: ...4 Flue system 10 3A 5 Air supply 11 3A 6 Water circulation 11 3A 7 Electrical supply 11 3A 8 Mounting on a combustible surface 11 3A 9 Timber framed buildings 11 3A 10 Inhibitors 11 3A 11 Showers 11...

Page 3: ...r Vok ra Compact SE boiler has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and efficiency Please there...

Page 4: ...ounter clockwise to reduce the temperature range 37 C 60 C Boiler at OFF standby Select this position when you want the boiler to be switched off for short periods days or if the boiler requires to be...

Page 5: ...ppliance fails to ignite during the ignition sequence it will enter a lockout condition Should this occur please allow a period of at least two minutes before re setting the appliance 2 6 EXPLANATION...

Page 6: ...f you think your boiler may have developed a fault please contact your installer or Vok ra Customer Services 0844 3910999 UK or 056 7755057 ROI have all your details to hand including full address and...

Page 7: ...a sealed system only consequently they are not intended for use on open vented systems This booklet is an integral part of the appliance It is therefore necessary to ensure that the booklet is handed...

Page 8: ...e minute anti cycle timer delay When the request for heat has been satisfied the appliance pump and fan may continue to operate to dissipate any residual heat within the appliance 1 4 MODE OF OPERATIO...

Page 9: ...ht mm 715 Width mm 405 Depth mm 248 Dry weight kg 28 2 6 Clearances Compact 24 SE Sides 12mm Top 150mm from casing or 25mm above flue elbow whichever is applicable Bottom 150mm Front 500mm 2 7 Connect...

Page 10: ...from a terminal on the same wall 300 mm P From a structure to the side of the vertical terminal 300 mm Q From the top of the vertical terminal to the roof flashing As determined by the fixed collar of...

Page 11: ...to which BS 5440 PART 1 FLUES BS 5440 PART 2 FLUES VENTILATION BS 5449 PART 1 FORCED CIRCULATION HOT WATER SYSTEMS BS 5546 INSTALLATION OF GAS HOT WATER SUPPLIES FOR DOMESTIC PURPOSES BS 6798 INSTALLA...

Page 12: ...1363 is acceptable 3 8 MOUNTING ON A COMBUSTIBLE SURFACE If the appliance is to be fitted on a wall of combustible material a sheet of fireproof material must protect the wall 3 9 TIMBER FRAMED BUILD...

Page 13: ...SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a position at least 1 metre above the highest point in the system and at least...

Page 14: ...flue applications to be considered alternatively the Vok ra twin flue system can be utilised if longer flue runs are required 4 5 2 CONCENTRIC HORIZONTAL FLUE For concentric vertical flue see 4 5 2 Fo...

Page 15: ...ion of the 90 bend Fig 12 Total flue length 60 100 Restrictor required Up to 1 85 metre 42 mm diameter From 1 85 to 3 35 metre 44 mm diameter From 3 35 to 5 25 metre Not installed NOTE These instructi...

Page 16: ...rough the ceiling and or roof Depending on site conditions it may be preferable to install the terminal assembly prior to fitting the twin flue pipes Fit the appropriate flashing plate to the roof and...

Page 17: ...2mm pipe to the inlet of each valve and tighten both nuts NOTE Depending on system requirements it may necessary to increase the size of the flow return pipe work after the service valve connections 4...

Page 18: ...ed as outlined below locate and unscrew the 2 screws A that secure the outer casing to the appliance lift the casing upward to disengage it from the top locating hooks and then remove store the casing...

Page 19: ...e gas rate then a combustion analysis test must be carried out in accordance with BS 7967 UK to ensure the appliance is left working safely and correctly Additionally if the gas valve has been adjuste...

Page 20: ...these instructions and explain the importance of keeping them in a safe place Explain to the user how to isolate the appliance from the gas water and electricity supplies and the locations of all drai...

Page 21: ...cking pin I from the pump assembly and remove the AAV assembly J Replace in the reverse order 6 8 WATER PRESSURE SWITCH fig 24 Carry out component removal procedure as described in 6 4 Locate and remo...

Page 22: ...the inner combustion cover and remove Disconnect the spark plug cable connection slide off the lower cable grommet from the seat of the air distribution box remove the burner fixing screws and remove...

Page 23: ...t the cold water inlet pipe at the DHW flow switch B2 Using a small screwdriver gently ease the flow restrictor C2 from its seating Replace in the reverse order Ensure all seals are in good condition...

Page 24: ...minutes timer delay When a new ignition sequence begins the output of the appliance is set at minimum for two minutes NOTE Any demand for hot water has the priority If there is a demand for hot water...

Page 25: ...umper JP2 turn the domestic hot water temperature adjustment knob C until it reaches the heating maximum value as indicated in the multigas table remove the jumper JP2 to store the heating maximum val...

Page 26: ...sing cycle the temperature value is restored to the value set by the user and the above mentioned cycle is repeated until the ambient thermostat request is fulfilled Fixed green if there is flame the...

Page 27: ...uminated See table on page 4 7 7 5 RESISTANCE TO EARTH CHECK Isolate the appliance from the electrical supply and using a suitable multi meter carry out a resistance test Connect test leads between th...

Page 28: ...4 VOK RA LOWER COVER MECHANICAL CLOCK fig 3 The Vok ra lower cover mechanical clock kit product code 20025081 is entirely suitable for the Compact 24SE and eliminates the need for an external time co...

Page 29: ...d LED Led 1 green working status or temporary stop Led 2 Not installed Led 3 red boiler lock out F1 Fuse 2A T F External fuse 3 15A F M3 Terminal strip for electrical connection hight power P Pump OPE...

Page 30: ...circuit board MP08 20005569 21 Led light guide 20013352 26 Control panel 20035608 27 Knob 20013055 31 Case Assembly 20026073 34 Fixing flange 20023928 90 Fuse R3478 470 Ignition transformer TR6 R1002...

Page 31: ...w actuator R10022349 27 Heating cock R1789 28 Connection R1790 30 Water supply stop cock R7099 36 Pipe 20005557 48 Cock 20000533 63 Pipe 20035609 201 Washer R5026 265 Washer R5236 266 Washer R5237 288...

Page 32: ...20029826 2 Pipe R10028603 3 Pump R10027571 4 Air vent bottle R10025485 7 Pipe 20005559 8 Heat exchanger 20005544 9 Pipe 20005558 200 Washer R5023 290 Clip R2165 299 Washer R10022726 302 Washer R5025...

Page 33: ...551 5 Spark ignition electrode R10025985 12 Gas pipe 20005554 13 Gas valve 20035533 14 Gas pipe 20005553 15 3 4 gas cock R10020897 16 Combustion chamber cover 20005594 17 Gas valve solenoid R10020838...

Page 34: ...ation panel 20005560 7 Flue draught diverter 20005596 10 Fan kit 20026724 11 Pressure connection 20021548 12 Fumes connection 20011048 13 Segnal amplifier 20025687 17 Washer 20005552 22 Flange 42 R100...

Page 35: ...ution box over and combustion chamber cover fig 22 disconnect the spark plug cable connection slide off the lower cable grommet from the seat of the air distribution box remove the burner fixing screw...

Page 36: ...ALL INSTALLATIONS If required by the manufacturer record the following CO2 OR CO ppm OR CO CO 2 Ratio The heating and hot water system complies with the appropriate Building Regulations Yes The boile...

Page 37: ...ignature SERVICE 7 Date Energy Efficiency Checklist completed Yes No Engineer Name Company Name Telephone Number CORGI ID Number Comments Signature SERVICE 9 Date Energy Efficiency Checklist completed...

Page 38: ......

Page 39: ......

Page 40: ...s vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve the...

Reviews: