Supplied By www.heating spares.co Tel. 0161 620 6677
11
Linea Plus AG
FITTING THE STANDARD (2359029)
HORIZONTAL FLUE KIT (see 5.4.1)
Carefully measure the distance from the centre
of the appliance flue outlet to the face of the
outside wall (dimension ‘X’ see fig. 13). Ensure
the inner (60mm) pipe is fully inserted into the
outer (100mm) pipe (when the inner pipe is
fully inserted, it stands proud of the outer pipe
by 7.5mm). Add 32mm to dimension ‘X’ to give
the overall flue lenghth (dimension 'Y')standard
horizontal flue kit (part no. 2359029) is suitable
for a distance (dimension ‘Y’) of up to 865mm.
NOTE
Dimension ‘Y’ is measured from the end of the
terminal to the end of the outer (100mm) pipe.
The internal trim should be fitted to the flue
pipe before connection of the 90º bend.
If the horizontal flue kit (2359029) requires to
be cut to the correct size (dimension ‘Y’), you
must ensure that the inner (60mm) pipe stands
proud of the outer (100mm) pipe by 7.5mm
(see fig. 13A). Ensure any burrs are filed or
removed and that any seals are located
properly before assembly.
Connect the inner (60mm) pipe of the terminal
assembly to the push-fit end of the 90º bend
(supplied) using a twisting action. Insert the
assembled flue into the previously drilled hole.
Using the clips & screws supplied, connect the
flue assembly to the boiler, ensuring that the
terminal protrudes past the finished outside
wall by the correct length (135mm).
You must ensure that the entire flue system is
properly supported and connected.
Seal the flue assembly to the wall using cement
or a suitable alternative that will provide
satisfactory weatherproofing. The exterior trim
can now be fitted.
Bend Reduction in maximum flue length for
each bend
45º bend
0.5 metre
90º bend
1.0 metre
Fig. 13
EXTENDING THE HORIZONTAL FLUE
If the horizontal flue requires extension/s or
additional bend/s, the horizontal flue terminal
kit (2359029) must be used. Connect the bend
– supplied with the terminal kit – to the top of the
boiler using the clips, screws, & gaskets
supplied. The additional bends & extensions
have an internal push-fit connection, care should
be taken to ensure that the correct seal is made
when assembling the flue system. Connect the
required number of flue extensions or bends
(up to the maximum equivalent flue length) to
the flue terminal using the clips, screws, &
gaskets supplied (see fig. 13 & 13A).
NOTE
When cutting the horizontal flue terminal or an
extension to the required length, you must
ensure that the excess is cut from the plain end
of the terminal or extension, and that the inner
(60mm) pipe is 7.5mm longer than outer
(100mm) pipe (see fig. 13 & 13A). Remove any
burrs, and check that any seals are located
properly.
You must ensure that the entire flue system is
properly supported and connected.
Seal the flue assembly to the wall using cement
or a suitable alternative that will provide
satisfactory weatherproofing. The interior and
exterior trim can now be fitted.
5.5.2
CONCENTRIC VERTICAL FLUE
The vertical flue terminal can be connected
directly to the appliance flue outlet. Alternatively,
an extension or bend can be connected to the
appliance flue outlet if desired (see 5.4.2),
however if additional bends are fitted, a reduction
must be made to the maximum flue length (see
table below).
Reduction for bends
Part No.
Description
Length
2359039
Vertical flue terminal
1.0 metre
0225770
Pitched roof flashing
N/A
plate
0225765
Flat roof flashing plate
N/A
2359069
750mm extension
750mm
2359079
1500mm extension
1500mm
2359049
45º bend (pair)
N/A
2359059
90º bend
N/A
0225760
Wall bracket (5)
N/A
Vertical flue terminal and accessories
Fig. 13A