A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
91
3.3 Specification of Connection Pipe
Size of Fitting Pipe
(
Inch
)
Liquid
Gas
Max
.
Pipe
Length
(
m
)
Max
.
Height
Difference
between
Indoor Unit
and Outdoor
Unit m
Amount of
Additional
Refrigerant to
be Filled
(
For
Extra Length
of Pipe
)
ACP-12CC35GECI 1/4”
3/8”
1/4”
1/2”
20
15
30
g
/
m
3/8”
5/8”
3/8”
5/8”
30
15
60
g
/
m
4 ELECTRIC WIRING WORK
4.1 Wiring Principle
4.1.1General
Perform wiring of the power supply in conformance with the regulations of the local electric company.
For the control wires connecting indoor units, and between indoor and outdoor units, use of double-core shield
wires is recommended to prevent noise trouble.
Be sure to set the earth leakage breaker and the switches to the power supply section of the indoor unit.
Supply power to each outdoor unit and provide an earth leakage breaker or hand switch for each outdoor unit.
Store wiring system for control and refrigerant piping system in the same line.
Arrange the cables so that the electric wires do not come to contact with high-temperature part of the
refrigerant pipe; otherwise coating melts and an accident may be caused.
Do not turn on power of the indoor unit until vacuuming of the refrigerant pipe will finish.
Installation should be conducted by National Wiring Regulation.
The rated voltage and exclusive power supply must be adopted for the air conditioners.
The power cable should be reliable and fixed, in order to avoid the wiring terminal be suffered from force. And
do not drag the power cable forcibly.
The wire diameter of power cable should be large enough, if power cable and connection wire be damaged, it
should be replaced by the exclusive cable.
All electric installation must be done by professional personnel according to local law, regulation and this
manual.
It should be reliably earthed, and it should be connected to the special earth device, the installation work
should be operated by the professional.
The creepage protect switch and air switch must be installed.
Air switch should have the thermal dropout and magnetic dropout function, in order to avoid the short circuit
and overload.
Item
Model
ACP-18CC50GECI
ACP-18CF50GECI
ACP-24CC70GECI
ACP-24CF70GECI
ACP-36CC100GECI
ACP-36CF100GECI
Summary of Contents for ACP-12CC35GECI
Page 2: ......
Page 3: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 1 PRODUCT ...
Page 15: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 22 CONTROL ...
Page 17: ...A A DC INVERTER U MATCH AIR CONDITIONERS CONTROL 24 1 2 Heating Operation ...
Page 52: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 59 5 3 7 Dimensions ...
Page 53: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 60 INSTALLATION ...
Page 76: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 99 MAINTENANCE ...
Page 95: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 118 IPM module protection ...
Page 96: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 119 DC busbar overvoltage protection ...
Page 97: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 120 DC busbar undervoltage protection ...
Page 98: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 121 Abnormal noise from PFC inductor ...
Page 99: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 122 Radiator overheat protection ...
Page 100: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 123 Tripping ...
Page 176: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 242 Model ACP 12CC35GECI Exploded View ...
Page 178: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 244 Model ACP 18CC50GECI Exploded View ...
Page 182: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 249 Model ACP 36CC100GECI Exploded View ...
Page 188: ......
Page 189: ......
Page 190: ......