A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
81
polythene pipe: Outer diameter 25mm Surface thickness
≥
1.5mm)
Drain hose should be short and drooping gradient should at less 1/100 to prevent the formation of air bubble.
If drain hose cannot has enough drooping gradient, drain raising pipe should be added.
To prevent bent of the drain hose, the distance between hoisting stand should is 1 to 1.5m. (As shown in Figure
1-3-8)
1-1.5m
○
(Correct) 1/100 or more gradient
×
(wrong)
Figure 1-3-8
The install height of the drain raising pipe should less than 280mm.
The drain raising pipe should form a right angle with the unit, and distance to unit should not beyond 300mm.
(As shown in Figure 1-3-9)
Celling
1-1.5m
Hanger bracket
Below
1120mm
Above
280mm
200mm
Drainage raising pipe
Drainage hose
(attachment)
Cassette type unit
with in 300mm
Clamp(attachment)
Figure 1-3-9
The slant gradient of the attached drain hose should be within 75mm so that the drain
hole
doesn’t has to
endure the unnecessary outside force. (As shown in Figure 1-3-10)
Drain hose(attachment)
.
Below75mm
Below50
0
mm
Figure 1-3-10
Please install the drain hose according to the following process if several drain hoses join together. (As shown
in Figure 1-3-11)
T-tie in join drain hose
Above100mm
.
The specs of the selected join drain hose should fits the running capacity of the unit.
Figure 1-3-11
Check the smoothness of drain after installation.
Check the drain state by immiting 600cc water slowly from the outlet vent or test hole. (As shown in Figure
1-3-12)
Check the drain in the state of refrigerating after installation of the electric circuit.
Summary of Contents for ACP-12CC35GECI
Page 2: ......
Page 3: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 1 PRODUCT ...
Page 15: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 22 CONTROL ...
Page 17: ...A A DC INVERTER U MATCH AIR CONDITIONERS CONTROL 24 1 2 Heating Operation ...
Page 52: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 59 5 3 7 Dimensions ...
Page 53: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 60 INSTALLATION ...
Page 76: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 99 MAINTENANCE ...
Page 95: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 118 IPM module protection ...
Page 96: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 119 DC busbar overvoltage protection ...
Page 97: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 120 DC busbar undervoltage protection ...
Page 98: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 121 Abnormal noise from PFC inductor ...
Page 99: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 122 Radiator overheat protection ...
Page 100: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 123 Tripping ...
Page 176: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 242 Model ACP 12CC35GECI Exploded View ...
Page 178: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 244 Model ACP 18CC50GECI Exploded View ...
Page 182: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 249 Model ACP 36CC100GECI Exploded View ...
Page 188: ......
Page 189: ......
Page 190: ......