A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
16
Continued
:
2
Indoor unit
ACP-36CF100GECI
Model
Outdoor unit
ACP-36CF100GECI
kW 10.6
Cooling
Btu/h 36160
kW 12
Nominal
Capacity
Heating
Btu
/
h
40940
Power
Cooling
kW 3.26
Input
Heating
kW
3.16
EER/COP
W
/
W
3.25/3.8
Indoor Unit
ACP-36CF100GECI
Power Supply
-
220-240V-50Hz-1Ph
Heat Exchange
-
Cross Fin Coil
Type
-
Centrifugal fan
Drive
-
Direct
Motor Output
kW
0.15
Fan
Air Flow
m3
/
h
2000
Sound Pressure Level(H/M/L) dB(A) 54/51/48
Air Filter
-
Standard washable synthetic
Drain Piping
mm
Φ
17×2.5
1420×245×700
Dimensions (W×H×D)
(Outline/Package)
mm
1545×330×825
Weight(Net/Gross)
kg 53/61
Outdoor Unit
ACP-36CF100GECI
Power Supply
-
220-240V-50Hz-1Ph
Heat Exchange
-
Cross Fin Coil
Type
-
Axial fan
Motor Output
kW
0.75×1
Fan
Fan Motor
Speed
0
2
±
0
2
8
m
p
r
Type
-
Y
R
A
T
O
R
Compressor
Power Input
W
3010±7.5%
Type
-
A
0
1
4
R
Control
-
Electronic Expansion Valve
Refrigerant
Charge
kg 3.5
1107×1100×440
Dimensions (W×H×D)
(Outline/Package)
mm
1155×1220×490
Weight(Net/Gross)
kg
86/97
Liquid
Inch
Φ
3/8"
Gas
Inch
Φ
5/8"
Piping
Connections
Max. Length
m 30
Max. Height Difference
m
15
Summary of Contents for ACP-12CC35GECI
Page 2: ......
Page 3: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 1 PRODUCT ...
Page 15: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 22 CONTROL ...
Page 17: ...A A DC INVERTER U MATCH AIR CONDITIONERS CONTROL 24 1 2 Heating Operation ...
Page 52: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 59 5 3 7 Dimensions ...
Page 53: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 60 INSTALLATION ...
Page 76: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 99 MAINTENANCE ...
Page 95: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 118 IPM module protection ...
Page 96: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 119 DC busbar overvoltage protection ...
Page 97: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 120 DC busbar undervoltage protection ...
Page 98: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 121 Abnormal noise from PFC inductor ...
Page 99: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 122 Radiator overheat protection ...
Page 100: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 123 Tripping ...
Page 176: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 242 Model ACP 12CC35GECI Exploded View ...
Page 178: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 244 Model ACP 18CC50GECI Exploded View ...
Page 182: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 249 Model ACP 36CC100GECI Exploded View ...
Page 188: ......
Page 189: ......
Page 190: ......