A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
87
Figure 3-1-1
Align the flared end of copper pipe with the center of threaded connector and use your hands to securely
tighten the flared nuts.
Tighten the flared nuts with torque wrench, until you hear a ‘KATA” sound from the torque wrench, as shown in
Fig. 3-1-1. See Table 3-1-1 for the torque required for tightening the nuts.
Figure 3-1-2
Form 3-1-1 the tightening torque needed for tightening nut
Pipe diameter
Tightening Torque
1/4
"(
Inch
)
15-30
(N·m)
3/8
"(
Inch
)
35-40
(N·m)
5/8
"(
Inch
)
60-65 (N·m)
1/2
"(
Inch
)
45-50
(N·m)
3/4
"(
Inch
)
70-75
N·m)
7/8
〞(
Inch
)
80-85
(N
·
m)
The bend of pipe shall not be too small; otherwise the pipe might be broken. Please use pipe bender to bend
the pipe.
Generally, the pipe shall be welded with the weld junction upward or horizontal. Avoid welding with the pipe
opening downward. (Downward welding is easy to cause defects, which may affect the weld quality or even
cause leakage, as show in Fig. 3-1-3).
Figure 3-1-3
Use sponge to wrap the connection pipes and connectors that are not thermally insulated, and tighten with
plastic tapes.
2
)
Vacuum and Leakage Detection
Remove the cap from liquid valve and gas valve.
Align with the pipe center and tighten the jointing nuts adequately with your hand.
Tighten the nuts with wrench.
Remove the 1-way cap from the gas valve.
Summary of Contents for ACP-12CC35GECI
Page 2: ......
Page 3: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 1 PRODUCT ...
Page 15: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 22 CONTROL ...
Page 17: ...A A DC INVERTER U MATCH AIR CONDITIONERS CONTROL 24 1 2 Heating Operation ...
Page 52: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 59 5 3 7 Dimensions ...
Page 53: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 60 INSTALLATION ...
Page 76: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 99 MAINTENANCE ...
Page 95: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 118 IPM module protection ...
Page 96: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 119 DC busbar overvoltage protection ...
Page 97: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 120 DC busbar undervoltage protection ...
Page 98: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 121 Abnormal noise from PFC inductor ...
Page 99: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 122 Radiator overheat protection ...
Page 100: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 123 Tripping ...
Page 176: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 242 Model ACP 12CC35GECI Exploded View ...
Page 178: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 244 Model ACP 18CC50GECI Exploded View ...
Page 182: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 249 Model ACP 36CC100GECI Exploded View ...
Page 188: ......
Page 189: ......
Page 190: ......