SPIRIT G XL 1-3 KVA - PF0.9 - UPS
www.visionups.com
33
(Bypass mode)
130%±5% ̶ 150%±5% : load transfers to fault mode after 2min
150%±5% ̶ 200%±5% : load transfers to fault mode after 15sec
>200%±5% : load transfers to fault mode after 140ms
Output overload
(Battery mode)
108%±5% ̶ 150%±5% : load transfers to fault mode after 30sec
150%±5% ̶ 200%±5% : load transfers to fault mode after 300ms
>200%±5% : load transfers to fault mode after 20ms
Wave form
Sine wave
Harmonic distortion
<3% THD on linear load
<5% THD on non-linear load
Transfer time
Online mode : 0ms (no break)
High efficiency mode ECO : 10ms maximum (due to loss of utility)
Power factor
0.9
Load crest factor
3 to 1
TABLE 18 – Electrical output connections (all models)
Model
Output connection
Output cable
1KVA –
RT
( IEC C13-10A ) *6
IEC 320 C14-10A
1.5KVA –
RT
( IEC C13-10A ) *6
IEC 320 C14-10A
2KVA –
RT
( IEC C13-10A ) *6
IEC 320 C14-10A
3KVA -
RT
( IEC C13-10A ) *6
( IEC C19-16A ) *1
IEC 320 C14-10A
IEC 320 C20-10A
TABLE 19 – Environment and safety (all models)
208 / 230 / 240Vac models
Surge suppression
EN 61000-2-2
EN 61000-4-2, level 4
EN 61000-4-3, level 3
EN 61000-4-4, level 4 (also on signal ports)
EN 61000-4-5, level 4 criteria A
EMC Certifications
CE per IEC/EN 62040-2
Class B
Class B
EMC (emissions)
IEC 62040-2:ed2:2005 / EN 62040-2:2006
Safety conformance
IEC 62040-1-1, IEC 60950-1
Agency markings
CE
Operating temperature
0°C to 40°C in Online mode, with linear derating for altitude
NOTE: Thermal protection switches the load to the bypass in case of overheating
Storage temperature
-20°C to 40°C with batteries
-25°C to 55°C without batteries
Transit temperature
-25°C to 55°C
Relative Humidity
0%-90% non-condensing
Operating altitude
Up to 3000 meters above sea level
Transit altitude
Up to 10000 meters above sea level
Audible noise
<55dBA at 1 meter typical
Leakage current
<1.5mA