SPIRIT G XL 1-3 KVA - PF0.9 - UPS
www.visionups.com
10
Follow these steps to install the UPS:
①
Remove the front cover of each UPS, hold and extract the right cover part (without LCD) from the
panel (see fig. 7).
②
Connect the internal battery connector red to red (see fig. 8). Press the connector firmly in to ensure
a proper connection.
Remark: Note that the above steps ① and ② are only concerning the replacement of batteries or
the addition of internal batteries. If the UPS is delivered with installed internal batteries, then the
plug is already connected.
CAUTION: A small electric arc may occur when connecting the internal batteries. This is normal and
will not harm personnel. Connect the cables quickly and firmly.
③
If you are installing EBPs, then read the following section «Connecting the Battery Packs (EBPs)»
before continuing with the UPS installation.
④
Replace the UPS front cover: if EBPs are installed, verify if the EBP cable has been well routed
through the knockout-opening in the knockout metal sheet before replacing the cover. Afterwards,
mount back the cover.
Fig. 7 – Extract the UPS front cover
Fig. 8 – Connection of internal batteries of the UPS
Fig. 9 – Connection of long backup external battery