SPIRIT G XL 1-3 KVA - PF0.9 - UPS
www.visionups.com
15
4. DISPLAY MONITOR, OPERATION AND CONTROL
This chapter contains information for use of the UPS, including front cover operation, operating modes, UPS start-up and
shutdown, transferring the UPS between the modes, configuring bypass settings, load segments and battery settings.
4.1. Control functions
The UPS has a LCD segmental display with three buttons and backlight. It provides useful information about the UPS itself,
load status, measurements and settings (see fig. 18).
TABLE 1 – Indicator descriptions
Indicator
Description
red
ON - The UPS has an active alarm or fault.
yellow
ON - The UPS is in bypass mode. The UPS is operating normally on bypass during ECO mode with high
efficiency operation.
yellow
ON - The UPS is in battery mode.
ON - The UPS is operating normally.
NOTE:
When the UPS is powered on or is in start-up process, these indicators will turn on and off sequentially.
NOTE:
On different operation modes, these indicators will indicate differently. Refer for that to table 7.
TABLE 2 – Button functions
Button
Function description
Start-up
combination
(
+
)
RT - Press and hold these keys longer than ½ second to turn on the UPS or to turn it off.
Rotating
combination
(
+
)
RT - Press and hold these keys longer than 2 seconds to circumrotate the LCD.
Battery
test/mute
combination
(
+
)
Press and hold these keys longer than 1 second in LINE mode or ECO mode: the UPS runs its self-test function.
Press and hold these keys longer than 1 second in battery mode: the UPS operates in mute function.
Scroll
or
Setting mode «without function»:
Press and hold this key longer than ½ second (but shorter than 2 seconds): indicates the items of LCD menu
orderly.
Press and hold this key longer than 2 seconds: indicates the items orderly and circularly (every two seconds);
when pressing and holding the key for some time again, it will return to the initial status.
Setting mode «with function»:
Press and hold this key longer than ½ second (but shorter than 2 seconds): select the set option.
Setting entry
Setting mode «without function»:
Press and hold the key longer than 2 seconds: function setting interface.
Setting mode «with function»:
Press and hold the key longer than ½ second (but shorter than 2 seconds): confirm the set option.
Press and hold the key longer than 2 seconds: exit from this function setting interface.
Fig. 18 – LED display functions