Chapter 4 Deployment TM-E
Manual VIPA TM-E
3-6
HB39E - TME - RE_900-1E650 - Rev. 09/11
Cabling
At the lower side of the TM-E module there are connectors for power
supply and digital inputs/outputs. The output is designed as low-side output
and may be configured.
The connectors are plugs with screw contacts. If connected the plugs may
be fixed with screws.
Pin
Name
Meaning
Digital input/output
1 DO_GND DO
ground
2
DO_OC
Digital output DC 24V, 0.2A
Low-side output
3
DO_VDC
DO load voltage DC 24V
4
DI_GND
DI ground (isolated)
5
DI
Digital input DC 0/24V
"0": 0 ... 5V DC
"1": 10V ... 30V DC
Power supply
1
GND
Ground power supply
1
.
.
.
5
1
2
2 12-24V
DC DC 12 ... 24V
±
20%
The TM-E module is to be supplied by DC 12...24V
±
20%. The connection
is established by means of a plug. This is at the lower side of the module
and has the following allocation:
Pin
Name
Meaning
1
GND
Ground power supply
1
2
2 12-24V
DC DC 12 ... 24V
±
20%
DO_GND 1
DC
24V
DO_OC 2
-
+
DO_VDC 3
DC
24V
+
-
DI_GND 4
DI 5
DC 24V
Output DO
Optocoupler
DO_GND
1
DO_OC
2
DO_VDC
3
+
-
Overview
Power supply
DI/DO wiring /
schematic
diagram