Manual VIPA TM-E
Chapter 4
Deployment TM-E
HB39E - TME - RE_900-1E650 - Rev. 09/11
3-17
•
For the VIPA PLC select as I/O server "S73&400". The following dialog
window is opened:
At "Gateway Configuration" and "MPI/Profibus Setup" the values are
preset, which are to be used per default.
- Destination node (Address of the destination node)
- Protocol type (standard: MPI)
- Baud rate (standard: 187500
- Reply Timeout (standard: 3000ms)
- MPI/Profibus Address (Address of the TM-E module, standard: 0)
- Highest MPI/Profibus Address (standard: 31)
At
Topic
... access paths to your PLC may be defined, assigned to a
corresponding
Topic
character and activated.
By presetting the key words MPI, PROFIBUS respectively ISOTCP and
adding an address, a corresponding access path may be defined.
Access
via
Profibus:
PROFIBUS, # (with # corresponds to the
Profibus address of your connected PLC)
Example: PROFIBUS, 5
Access via MPI:
MPI, # (with # corresponds to the MPI address of
your PLC)
Example: MPI, 2
Access via IP address: ISOTCP,IP address,00.02
Enter each without spaces and always add to the
IP address ",00.02".
Example: ISOTCP,192.16.167.123,00.02
Enter at
Poll Rate
the standard value 2000ms and click at [Update config].
I/O server
configuration