Manual VIPA CPU 21x
Chapter 1
Principles
HB103E - Rev. 05/45
1-9
Hints for project engineering
For the project engineering of the CPU 21x and the other System 200V
modules connected to the same VIPA bus, you use the hardware
configurator from Siemens.
To address the directly plugged peripheral modules, you have to assign a
special address in the CPU to every one.
The address allocation and the parameterization of the modules takes
place in the SIMATIC manager from Siemens in form of a virtual Profibus
system. For the Profibus interface is standardized software sided, the
functionality is guaranteed by including a GSD-file into the SIMATIC
manager from Siemens.
Transfer your project into the CPU via the MPI interface.
For the project engineering of your CPU 21x the following requirements
have to be fulfilled:
•
SIMATIC manager from Siemens is installed at your PC resp. PG.
•
The GSD-file for the System 200V is included to the hardware
configurator. Actual GSD files can be found at ftp://ftp.vipa.de/support.
•
serial connection to the CPU (e.g. via "Green Cable" from VIPA)
Note!
The configuration of the CPU requires a thorough knowledge of the
Siemens SIMATIC manager and the hardware configurator!
The project engineering of a CPU 21x takes place via the SIMATIC mana-
ger from Siemens in form of a virtual Profibus system with the
CPU 315-2DP as basic.
Due to the standardized Profibus interface VIPA is able to support the
complete functionality of the System 200V family in the SIMATIC manager
from Siemens by including the GSD-file vipa_21x.gsd.
To be compatible with the SIMATIC manager from Siemens, the following
steps have to take place:
•
Project the Profibus-DP master system with CPU 315-2DP
(6ES7 315-2AF03 V1.2).
•
Add Profibus slave "VIPA_CPU21x" from the HW catalog with address 1.
•
Include the CPU 21x at the 1
st
slot of the slave system.
Outline
Preconditions
Compatibility to
SIMATIC manager
from Siemens via
vipa_21x.gsd
GSD-file
Summary of Contents for CPU 21 Series
Page 1: ...Manual VIPA CPU 21x Order No VIPA HB103E Rev 05 45 ...
Page 2: ...Lerrzeichen ...
Page 6: ...About this Manual Manual VIPA CPU 21x Subject to change to cater for technical progress ...
Page 10: ...Contents Manual VIPA CPU 21x iv HB103E Rev 05 45 ...
Page 30: ...Chapter 1 Principles Manual VIPA CPU 21x 1 18 HB103E Rev 05 45 ...
Page 58: ...Chapter 2 Hardware description Manual VIPA CPU 21x 2 28 HB103E Rev 05 45 ...
Page 80: ...Chapter 3 Deployment CPU 21x Manual VIPA CPU 21x 3 22 HB103E Rev 05 45 ...
Page 178: ...Chapter 5 Deployment CPU 21x 2BT02 with H1 TCP IP Manual VIPA CPU 21x 5 48 HB103E Rev 05 45 ...