9 . 5 R e s e t t i n g t h e C O R R IGO
In some cases, after multiple settings or following a malfunction, it is sometimes necessary to reset the
programme controller.
After having cut the electrical power supply to the unit at the safety switch, open the door giving access to
the controller. Remove the connectors on the CORRIGO except the one for power.
A 05 95
A 04 94
A 03 93
A 02 92
A 01 91
Agnd 90
DI 8 78
DI 7 77
DI 6 76
DI 5 75
DI 4 74
DI 3 73
DI 2 72
E 63
Ext.
Disp.
N 62
A 61
B 60
E 53
P
1
A 51
B 50
P
2
P 1 Rx
Tx
P 2 Rx
Tx
TCP / IP
P / B
N 52
DI 1 71
TCP / IP
45 UI4
44 UI3
43 Agnd
42 UI2
41 UI1
40 A
GND
35 AI4
34 AI3
33 Agnd
32 AI2
31 UI1
30 Agnd
17 D07
16 D06
15 D05
14 D04
13 D03
12 D02
11 D01
10 GD0
4 +C
2 G0
-
1
G+
TCP / IP
45 UI4
44 UI3
43 Agnd
42 UI2
41 UI1
40 A
GND
35 AI4
34 AI3
33 Agnd
32 AI2
31 UI1
30 Agnd
17 D07
16 D06
15 D05
14 D04
13 D03
12 D02
11 D01
10 GD0
4 +C
2 G0
-
1
G+
A 05 95
A 04 94
A 03 93
A 02 92
A 01 91
Agnd 90
DI 8 78
DI 7 77
DI 6 76
DI 5 75
DI 4 74
DI 3 73
DI 2 72
E 63
Ext.
Disp.
N 62
A 61
B 60
E 53
P
1
A 51
B 50
P
2
P 1 Rx
Tx
P 2 Rx
Tx
TCP / IP
P / B
N 52
DI 1 71
Using a screwdriver, unclip the CORRIGO from the DIN rail.
To perform the reset operation, the
CORRIGO must be turned on. Switch
on the unit by turning on the safety
switch.
With the aid of a thin rod (trombone
type), reset the CORRIGO.
Clip the CORRIGO to the DIN rail by
performing the inverse manipulation of
unclipping, without reconnecting the
connectors except that of the remote
control.