NT00000535-KSDR-ECOWATT-48-88-120-160-200-AN-190905
23/88
ENGLISH
6 . 1 . 2 C O R R l GO C o n t r o l l e r
•
Supply voltage 24 Vac ±15%, 50 to 60 Hz or 21 to 36 Vdc
•
Power consumed models E.W-3: 12 VA, 6 W (DC)
•
Ambient temperature 0...50°C
•
Storage temperature -40...+50°C
•
Max. ambient humidity 90% RH
• Protection index IP20
•
Connecting plug-in terminals, 4 mm2
•
Memory Backup: an integrated long-life battery allows saving long-time settings, real time included.
El e c t r o m a g n e t i c c o m p a t i b i l i t y ( EM C ) d i r e c t i v e
This product meets the requirements of the Directive 2004/108/CE of the European Parliament and
Council (CEM) through compliance with standards EN 61000-6-1 and EN 61000-6-3.
R o HS
This product meets the requirements of the Directive 2011/65/UE of the European Parliament and Coun
-
cil.
In p u t s
Analog inputs for PT1000 sensors (preI- 0.4 °C) or 0...10 Vdc (preI- 0.15% of the whole
output signal). 12-bit resolution in the A/D signal conversion. Digital Inputs for potential-free contacts.
O u t p u t s
Analog outputs 0...10 Vdc, 1 mA, protection against short-circuits. Digital outputs, Mosfet outputs, 24 V
AC/DC, 2 A continuous. Max. 8 A in total.
C o m m u n i c a t i o n p o r t s
1 Web server TCP/IP port, TCP/IP communication,, BACnet/IP.
2 Modbus communication and EXOline RS485 Ports (language REGIN).
In d i c a t i o n s
Operation:
The green LED is lit when the CORRIGO is turned on.
Alarm:
The red LED flashes and the alarm text is displayed on the screen.
General alarm:
This output can be configured.
E tool© configuration software
Equipment required: operating system MS Windows 2000, 8, 7, XP, Vista, Windows 7, Windows 8 or
Windows 10 available on www.vim.fr.