NT00000535-KSDR-ECOWATT-48-88-120-160-200-AN-190905
61/88
ENGLISH
1 0 . 2 B a c n e t c o m m u n i c a t i o n p r o t o c o l e f o r B M S c o m m u n i c a t i o n
B A C n e t M S/ T P O N p o r t 2 – R S4 8 5
(BACnet MS/TP)
P1 RxTx
TCP/IP P/
B B 50
A 51 N 52 E 53 B 60 A 61 N 62 E 63
P2 RxTx
CORRIGO
P 1
P 2
The regulator CORRIGO has 2 communication ports RS485 (to use with
a cable STP), the port2 is dedicated by default to the communication in
BACnet MS / TP, but the function must be activated to be able to work.
B A C n e t a c t i v a t i o n
Advanced settings
Central Simple flux
2016-01-10
System : normal
C:19.5C/R: 20.0C
x5
x 29
x 2
Function port2 :
BACnet MS/TP
communication
Port2
Not active
Activate the BACnet MS/TP
Device name :
Corrigo Ventilation
MAC
0
To change the name or MAC click on Modify the value in Highlighting
Device ID low
2640
Device ID high
0 (10000)
To change ID low or high click on Modify the value in Highlighting
Speed
9600bps
Max master address
127
To change speed click on Modify the value in Highlighting with arrow and valid
Temperature
Air control
Time settings
Acces rights
Log on
enter password:***
Actual level: None
Log on
Log off
Change password
With the arrow up and down enter password 1111 after each
digit click on right arrow to go to the next one. at the end click on
Log on
enter password:1111
Actual level: None
Log on
enter password:1111
Actual level: Admin
Log on
Log off
Change password
Pretreatment
Alarm settings
Communication
Other parameters
Manual/Auto
Control function
Configuration
Acces right
Input/output
sensor settings
Control function
fan control