P R ESENT A T IO N O F R A NGE - P R O D U C T
2 . 1 R a n g e
U s e
: Supply of fresh air into buildings with heating or cooling. Installation on feet, inside or outside.
5 Si ze
s
: 48 (4,800 m³/h), 88 (8,800 m³/h), 120 (12,000 m³/h), 160 (16,000 m³/h), and 200 (20,000 m³/h).
•
M o d e l s w i t h i n t e g r a t e d c o i l s :
-
EC
: heating coil.
-
EF
: cooling coil.
-
ER
: reversible heating coil/cooling coil, 3, 4, 6 or 8 rows.
-
EC F
: heating coil + cooling coil.
-
ER C
: reversible coil + heating coil
-
EI
: electric heater.
-
EIX
: electric heaters for preh DX coil.
-
EX
: DX coil
•
Configurations:
-
D
: Indoor version, right-hand access in the direction of the air.
-
G
: Indoor version, left-hand access in the direction of the air
-
EX D
: Outdoor version, right-hand access in the direction of the air.
-
EX G
: Outdoor version, left-hand access in the direction of the air.
•
C o n s t r u c t i o n s :
-
Monoblock sizes 48 to 120,
-
Bi-block sizes 160 and 200: 1 casing with filtration, control and ventilation, and 1 casing with the thermal
coils.
•
D a m p e r s
-
Si z e s 4 8 t o 8 8 : d e l i v e r e d w i t h o u t t h e d a m p e r
-
Motorised dampers are available as accessories (following table)
-
Suction setting for antifreeze protection of water coils
-
Blowing setting to comply with CH 38 article of Public Access Buildings (ERP) French regulation.
K SD R s i z e s
C o d e
A c c e s s o r y d e s i g n a t i o n
D e s c r i p t i o n
48
170286
C D R 1 0 0 F 8 0 0 x 6 1 0
Motorisable antifreeze or fire damper
88
170349
C D R 1 0 0 F 1 1 0 0 x 9 1 0
Motorisable antifreeze or fire damper
-
Si z e s 1 2 0 t o 2 0 0 : d e l i v e r e d w i t h d a m p e r ( o p t i o n a l o n M o d e l 1 2 0 EI w i t h e l e c t r i c a l h e a t e r )
-
Motorised damper fitted as standard inside the AHU
-
Dual function: antifreeze protection of the water coils and compliant with article CH 38 of the ERP, Public
Access Buildings French regulation.
K SD R s i z e s w i t h i n t e r n a l d a m p e r
EC
EF
ER
EC F
ER C
EI
120
160
200
Included,
Option
R e m i n d e r o f a r t i c l e C H 3 8 , P u b l i c A c c e s s B u i l d i n g s F r e n c h r e g u l a t i o n :
Obligation to provide a metal
damper downstream of the filters, controlled by a DAD (Autonomous Detector Trigger) for the AHU (whatev
-
er the flow) serving sleeping areas and the AHUs handling more than 10,000 m³/h.
•
C o m m u n i c a t i n g c o n t r o l l e r a s s e m b l e d / w i r e d r e a d y t o b e c o n n e c t e d :
-
Variable airflow (VAV), constant airflow (CAV), constant pressure (COP).
-
The ASR ECOWATT system for interlocked association with a KUBAIR F400 ECOWATT or a TED F400
ECOWATT - Consult the manual "NT00000438-SYSTEME-ASR-ECOWATT" available on www.vim.fr.
-
Temperature control by the included CORRIGO controller specific to VIM.
-
Modbus communicating on RS485 port and Bacnet IP on TCP/IP port.
-
ETD remote touch display included (10 m cable).