NT00000535-KSDR-ECOWATT-48-88-120-160-200-AN-190905
47/88
ENGLISH
8 . 6 . 3 A d a p t a t i o n o f t h e t e m p e r a t u r e s e t p o i n t a c c o r d i n g t o t h e e x t e r n a l t e m p e r a t u r e
Parameter
Constant supply air T°C with
outdoor T°C compensation
Heating mode
Outdoor air temperature
Compensation curve
Supply air
T°C setpoin
t
-30 -20
-10
0
10
14
20
18
22
26
The control operation is similar to the 1
st
case.
Instead of a single temperature setpoint, a compensation curve is defined by the factory with eight set
-
points.
The supply setpoint is thus adapted in relation to this curve, and the variation of plus or minus 3 °C is still
possible from the main screen. The required external temperature sensor is provided and mounted, and
the supply air temperature sensor is provided for attachment to the supply duct.
8 . 6 . 4 In p u t o f t e m p e r a t u r e s e t p o i n t
An initial setpoint value can be defined from the “Temperature'' screen in the menus . The setpoint is set
by default to 21°C and can be adjusted between 12 and 30 °C.
Main screen:
Access to adjustement
menu
21.4°C
2012 -06-26 14:02
2500 m3/h
Run mode : ON
Maintenance needed
Menu screen:
Select «Temperature»
menu
Menu
Temperature
Ventilation control
+21 .0° C
Desired (S&P.)
Extract T°
+21 .9° C
+10 .8° C
Room T°
Constant supply air temperature
+20 .9° C
Supply T°
Pass word:
OK
0
8
7
9
4
5
6
3
2
1
Enter PIN code:
Cancel
1111
Enter PIN code: 1111
and select: OK
Insert temperature setpoint:
OK
0
8
7
9
4
5
6
3
2
1
Setpoint
Cancel
C
Set temperature value
and select: OK
21.4°C
2012-06-26 14:02
2500 m3 /h
Etat du système : Marche
The user can vary the temperature from the main screen by +/- 3°C with
respect to this initial setpoint.
8 . 7 T e m p e r a t u r e c o n t r o l w i t h D X c o i l , EX a n d EIX v e r s i o n s
8 . 7 . 1 Ge n e r a l In f o r m a t i o n
A communication package, ''AHU Kit'', must be provided by the supplier of the group. It makes communi
-
cation possible between the DX coil group and the Corrigo.
The control mode of the DX coil is chosen on the touch display.
T e m p e r a t u r e c o n t r o l b y t h e D X g r o u p
The DX group controls the temperature control from its own sensors.
In this type of installation, the Corrigo does not ensure the temperature control functions. The sensors
supplied with the KSDR must remain installed.
Corrigo → DX Group
DX group → Corrigo
Authorization to start
De-frosting
A 0-10 V proportional heating/cooling signal from the Corrigo can be used.