NT00000535-KSDR-ECOWATT-48-88-120-160-200-AN-190905
62/88
ENGLISH
B A C n e t IP o n p o r t T C P / IP
TCP/IP
45 UI
4
44 UI
3
43 Agnd
42 UI
2
41 UI
1
40 Agnd
35 AI4
34 AI3
33 Agnd
(BACnet TCP/IP
ou Modbus TCP/IP)
The regulator CORRIGO has 1 communication ports TCP/IP to be
connect with the TCP/IP network. This port has to be be configured to
work on BACnet IP communication protocol
A c t i v a t i o n d u B A C n e t IP
Advanced settings
Central Simple flux
2016-01-10
System : normal
C:19.5C/R: 20.0C
x5
x 29
x 2
TCP/IP
DHCP:Yes
Set static IP
Current IP
169.254.209.126
Communication
BACnet /IP
Inactive
To activate the BACnet click on Change from NOt active to active with the arrow and valid
Device name
CORRIGOVentilation
BBMD address
To change the name click on Modify the value in Highlighting
Device ID low
2640
Device ID high
0 (10000)
To change the ID low and high value click on Modify the value in Highlighting
To change the UDP port click on Modify the value in Highlighting
UDP port number low
7808
UDP port number high
7 (x10000)
Temperature
Air control
Time settings
Acces rights
Log on
enter password:***
Actual level: None
Log on
Log off
Change password
Log on
enter password:1111
Actual level: None
With the arrow up and down enter password 1111 after each
digit click on right arrow to go to the next one. at the end click on
Log on
enter password:1111
Actual level: Admin
Log on
Log off
Change password
Manual/Auto
Control function
Configuration
Acces right
Pretreatment
Alarm settings
Communication
Other parameters
Input/output
sensor settings
Control function
fan control
It is possible to give a static ip address to the CORRIGO (similar procedure as with Modbus IP).