To change pressure sensor specifications:
Advanced settings
Central Simple flux
2016-01-10
System : normal
C:19.5C/R: 20.0C
x5
With the arrow up and down enter password 1111 after each
digit click on right arrow to go to the next one. at the end click on
Pressure VAS
0.5V: 0.0 Pa
4.5V: 800.0 Pa
(ex.)
Filter factor: 0.2
Pressure VAS2
0.5V: 0.0 Pa
4.5V: 800.0 Pa
(ex.)
Filter factor: 0.2
P Band and I Time
The proportional band and the integration time can be set for each unit.
This can improve reactivity and especially the phenomena of pumping and instability.
The values in the previous table are default values, they can be adjusted as needed for your installation.
Procedure to follow with the touch screen after confirming the password 1111 as here above:
- In CAV or VAV mode, the VAS pressure sensor allows air flow control and reading.
- In COP mode, the VAS pressure sensor allows pressure regulation.
In this mode, the VAS2 pressure sensor allows air flow reading.
Fill in the operating ranges in Volts and Pa as for the password above and confirm with the
Fill running ranges with Volts and Pa, confirm like for password here above
and confirm with the
Temperature
Air control
Time settings
Acces rights
Log on
enter password:***
Actual level: None
Log on
Log off
Change password
Log on
enter password:1111
Actual level: None
Manual/Auto
Control function
Configuration
Acces right
Input/output
sensor settings
Control function
fan control
Log on
enter password:1111
Actual level: Admin
Log on
Log off
Change password
Pressure control SAF
P-Band: 500.0 Pa
I-Time: 8.0 s
Min. Output: 15%
Manual/Auto
Settings
Configuration
Acces rights
Control temp
Control flow
Alarm settings
Log on
enter password:1111
Actual level: Admin
Log on
Log off
Change password