background image

Vitorond 200, VD2A Series Installation

2

5354 788 - 0c

 

Safety, Installation and Warranty Requirements

Safety

Please ensure that these instructions are read and understood before commencing installation. Failure to comply with 

the instructions listed below and details printed in this manual can cause product/property damage, severe personal 

injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information 

found in manual subsections).

WARNING

Installers must follow local regulations with respect 

to installation of carbon monoxide detectors. 

Follow the Viessmann maintenance schedule of the 

boiler in the “Service Instructions” manual.

  

Product documentation

 

Read all applicable documentation before commencing  

 

installation. Store documentation near boiler in a 

     readily accessible location for reference in the future  

 

by service personnel.

 

For a listing of applicable literature,

     please see section entitled “Important

     Regulatory and Safety Requirements”.

  

Advice to owner

     Once the installation work is complete, the heating  

 

contractor must familiarize the system operator/ 

 

ultimate owner with all equipment, as well as safety  

 

precautions/requirements, shutdown procedure, and  

 

the need for professional service annually before the

     heating season begins.

  

Licensed professional heating contractor

     The installation, adjustment, service and maintenance  

 

of this equipment must be performed by a licensed

   professional heating contractor.

 

Please see section entitled 

 

“Important Regulatory and Installation 

 Requirements”.

  

Contaminated air

   Air contaminated by chemicals can cause by-products  

 

in the combustion process, which are poisonous to 

 

inhabitants and destructive to 

 Viessmann 

equipment.

 

For a listing of chemicals which 

 

cannot be stored in or near the

     boiler room, please see section 

 

entitled “Mechanical Room”.

 

in this manual.

  

Warranty

     Information contained in this and 

 

related product documentation must 

 

be read and followed. Failure to do 

 

so renders the warranty null and void.

  

Carbon monoxide

     Improper installation, adjustment, service and/or  

 

maintenance can cause flue products to flow into 

 

living space. Flue products contain poisonous carbon  

 monoxide 

gas.

 

For information pertaining to the 

 

proper installation, adjustment, service 

 

and maintenance of this equipment to 

 

avoid formation of carbon  monoxide, 

 

please see section entitled “Combustion

 

air supply” and “Venting information” 

 

in this manual.

  

Fresh air

  

This equipment requires fresh air for 

 

safe operation and must be installed 

 

ensuring provisions for adequate 

 

combustion and ventilation air exist.

 

For information pertaining to the 

 

fresh air requirements of this product, 

 

please see subsection entitled 

 

“Mechanical Room” in this manual.

  

Equipment venting

 

Never operate boiler without an installed venting  

 

system. An improper venting system can cause 

 

carbon monoxide poisoning.

 

For information pertaining to 

 venting 

and chimney requirements, 

 

please see section entitled “Venting 

 Information” 

in 

this manual. All 

 

products of combustion must be 

 

safely vented to the outdoors.

Summary of Contents for VITOROND 200 VD2A-125

Page 1: ...he installation service and maintenance of hot water heating boilers There are no user serviceable parts on the boiler burner or control Ensure main power supply to equipment the heating system and al...

Page 2: ...by a licensed professional heating contractor Please see section entitled Important Regulatory and Installation Requirements Contaminated air Air contaminated by chemicals can cause by products in the...

Page 3: ...mist respirator Wear long sleeved loose fitting clothing gloves and eye protection Wash work clothes separately from other clothing Rinse washer thoroughly Operations such as sawing blowing tear out a...

Page 4: ...t Information 8 New Casting Design and Therm Control Functionality 9 Redesigned Return Water Distribution System 9 Therm Control Low Temperature Protection Logic 10 Mechanical Room 11 Minimum Clearanc...

Page 5: ...rior to Start up 35 Start up Information 36 Initial start up 36 Instructing the system user 36 Shut down 36 Extended shut down periods 36 Start up after extended shut down 36 Piping in Heating Cooling...

Page 6: ...Note We offer frequent installation and service seminars to familiarize our partners with our products Please inquire In Canada all electrical wiring is to be done in accordance with the latest editi...

Page 7: ...boiler Technical Data Manual Installation Instructions Service Instructions Operating Instructions and User s Information Manual Positive Pressure Venting Systems installation instructions Instructio...

Page 8: ...mperatures in excess of those listed will result in damages and will render warranty null and void About these Instructions Take note of all symbols and notations intended to draw attention to potenti...

Page 9: ...ess on the heat exchanger and in conjunction with the Vitotronic Therm Control logic prevents the formation of flue gas condensate at all return water temperatures eliminating the need for a shunt pum...

Page 10: ...eed for a shunt pump or return temperature elevation provided by a Low Temperature Protection LTP Package Example Take a heating system with one heating circuit and a mixing valve In the start up phas...

Page 11: ...e IMPORTANT Maintain 1 in 25 mm air clearance from uninsulated hot water pipes to combustible material Boiler model VD2A 125 160 195 230 270 a Minimum Clearance in front of boiler in mm 47 1200 53 140...

Page 12: ...ief opening 5 minutes of high fire full load burner operation Use the flame of a match or a candle or an approved test 6 After it has been determined that each appliance remaining connected to the com...

Page 13: ...a with adjustable anti vibration feet optional 1 73 in 44 mm 1 Boiler base length Boiler model 125 24 in 600 mm Boiler model 160 30 in 770 mm Boiler model 195 37 in 940 mm Boiler model 230 44 in 1110...

Page 14: ...el CAUTION The tilting of the cast iron section could cause injuries and damage to the boiler The cast iron sections have to be supported before assembling with the field supplied support A 4 The cast...

Page 15: ...ion Set up Assembly of Boiler Base continued 6 Cross bar larger cut out moves to its end during cast assembly 7 Complete assembling the cast iron sections 8 Finish levelling the boiler by using a leve...

Page 16: ...cover and remove it also remove studs 5 Remove distribution tube from boiler 6 Loosen and remove the tie rods 7 Remove rear section also remove studs from boiler return port Only applicable if the bo...

Page 17: ...and dry properly 2 Lift rear section onto the boiler base Make sure the section legs are in the base channel Properly position rear section and secure against tipping B Arrow pointing to rear Arrow p...

Page 18: ...ted with the supplied linseed oil and graphite based sealant before use IMPORTANT Each intermediate section has arrows on sides of the casting The arrows must be pointing up when laying flat and durin...

Page 19: ...icone ensure that the work area is properly ventilated 1 Loosen pressure nuts and remove draw tool kit 2 Ensure that the heat exchanger block is level and vertical on boiler base All individual sectio...

Page 20: ...distribution pipe openings are facing upward IMPORTANT Ensure the notch of the distribution tube cap is facing up and matching the slot in the cast iron Legend A Gasket B Distribution pipe C M12 studs...

Page 21: ...ple ports for leakage by sliding a piece of cardboard or paper underneath the cast iron block 7 When pressure vessel is tight release pressure carefully and slowly A hydrostatic pressure test is manda...

Page 22: ...oriented to prevent scalding of attendants IMPORTANT Removal of air from system water must occur via use of air vent s To ensure the boiler can be purged of all air ensure supply return water lines d...

Page 23: ...l be located close to the valve outlet 2 The discharge from safety or safety relief valves shall be so arranged that there will be no danger of scalding attendants When the safety or safety relief val...

Page 24: ...f a LWCO in all instances 1 Install supply and return headers complete with pressure gage temperature gage air vent low water cut off boiler drain valve and bypass pump Pipe up to isolation valves Clo...

Page 25: ...lts A into threaded openings of the rear section 2 Install rear insulation blanket 3 Install rear panels 4 Install Temp control sensor aJA A between third and fourth section counting from the back 5 T...

Page 26: ...mm 3 Run thermal sensor through cut outs on the back 4 Mount front brackets 5 Use butterfly nuts 6 Use supplied spring and tighten the blanket to the boiler as illustrated All components required for...

Page 27: ...on 1 Drill four d in 3 mm holes on the side panel as shown For left side mount use a mirror image of the drawing 2 Punch a 7 8 in 22 mm opening 3 Install control harness bracket using supplied 8 32 se...

Page 28: ...athead screw driver Mount control housing on the side panel 7 Secure control housing using two supplied screws 8 Run capillaries and boiler temperature sensor through 7 8 in 22 mm opening on side pane...

Page 29: ...t 1 to 2 m from the breeching outlet located at the rear of the boiler Venting Connections WARNING When installing or insulating overhead piping or venting do not stand on top panel of boiler Advise o...

Page 30: ...t possible way with a minimal number of elbows If necessary rearrange existing water piping to achieve closest possible chimney connection Avoid long horizontal runs of vent pipe H Horizontal runs mus...

Page 31: ...tions for the positive pressure venting system 1 Connect the flue outlet with the shortest possible run and with a slight upward slope to the chimney stack Avoid sharp bends in the flue path Flue outl...

Page 32: ...d 200 VD2A boiler series in the Technical Data Manual Burners For technical details see Technical Data Manual and or manufacturer s burner manuals supplied with burner Only oil or gas fired burners of...

Page 33: ...64 Burner manufacturer Weishaupt or Riello Burner Gas train approval Standard approvals are CSA for Canada and UL for U S IRI and FM approved equipment is also available please inquire Electrical requ...

Page 34: ...ht occur an antifreeze may be added to the system water to protect the system Please adhere to the specifications given by the antifreeze manufacturer Do not use automotive silicate based antifreeze W...

Page 35: ...system and switch the burner to automatic j Check all gaskets and connections and retighten if necessary j Check and retighten bolts of combustion chamber door and clean out opening covers several day...

Page 36: ...owner is made familiar with the functioning of the system its activation and its shut down The following topics must be covered H Proper system operation sequence H Explain the equipment as well as th...

Page 37: ...ust be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle Check installation instructions of chiller manufacturer ca...

Page 38: ...th with Vitotronic control side mounted dimension e in mm 40b 1030 40b 1030 40b 1030 40b 1030 40b 1030 Total width dimension d in mm 34 860 34 860 34 860 34 860 34 860 Total height with boiler base di...

Page 39: ...erature 4 fixed high limit F C 250 121 250 121 250 121 250 121 250 121 Max allow operating pressure 5 psig 85 85 85 85 85 Boiler connections 6 Boiler supply and return in 2 2 2 2 2 Drain valve sedimen...

Page 40: ...Technical information subject to change without notice Printed on environmentally friendly recycled and recyclable paper 5354 788 03 Vitorond 200 VD2A Series Installation...

Reviews: