62
Deleting the fault codes from the fault memory
Press the following keys:
1.
d
+
å
simultaneously for approx. 4 s.
The
"Service"
menu appears.
2.
|
/
~
for
"Fault history"
.
3.
d
to confirm.
4.
|
/
~
for
"Delete"
.
5.
d
to confirm.
6.
|
/
~
for
"Yes"
.
7.
d
to confirm.
8.
ä
until the default display is shown.
Fault codes
Fault code dis-
played
System characteristics
Cause
Measures
AA
■
Boiler circuit pump on
■
Return temperature raising
facility open
■
Buffer cylinder control valve
open
■
Too much wood charg-
ed.
■
Incorrect set value se-
lected at programming
unit.
■
Faulty system compo-
nent (pump, valve or
temperature sensor).
■
Activate "Dissip excess heat"
function.
■
Check the buffer cylinder temper-
ature before heat up and before
recharging fuel. Can the expec-
ted energy be drawn off or stor-
ed?
■
Check the boiler circuit pump,
valve of the return temperature
raising facility and temperature
sensor.
■
Press reset button for high limit
safety cut-out (only possible with
boiler water temperature below
70 °C) and acknowledge the
fault.
AB
Control mode
Water pressure is too low. Notify heating contractor.
AC
Control mode
Water pressure is too
high.
Notify heating contractor.
20
Control mode
Short circuit, flow temper-
ature sensor
Check flow temperature sensor
21
Control mode
Short circuit, boiler return
temperature sensor
Check boiler return temperature
sensor
22
Control mode
Short circuit, flue gas tem-
perature sensor
Check the flue gas temperature
sensor
24
Control unit set to 0 °C out-
side temperature
Short circuit, outside tem-
perature sensor
Check outside temperature sensor
25
No DHW heating
Short circuit, top buffer
temperature sensor
Check top buffer temperature sen-
sor
26
Control mode
Short circuit, centre buffer
temperature sensor
Check centre buffer temperature
sensor
27
Control mode
Short circuit, bottom buffer
temperature sensor
Check bottom buffer temperature
sensor
30
Control mode
Lead break, flow tempera-
ture sensor
Check flow temperature sensor
31
Control mode
Lead break, boiler return
temperature sensor
Check boiler return temperature
sensor
32
Control mode
Lead break, flue gas tem-
perature sensor
Check the flue gas temperature
sensor
Troubleshooting
Fault display
(cont.)
5777 985 GB
Diagnosis