34
Measure
Every 350
hours run
Once a
year
Every 3
years
Every 5
years
Check the system pressure.
X
Clean the hopper.
X
Clean the secondary heating surfaces and flue gas collec-
tor chamber.
X
Clean the ash chamber and combustion chamber.
X
Clean flue gas fan.
X
Clean the flue pipe.
X
Check the flue pipe for flue gas tightness and reseal if re-
quired.
X
Check the draught limiter function, oil and adjust.
X
Clean the Lambda probe.
X
Clean the air dampers.
X
Clean the air box and secondary air supply.
X
Clean the sensor well for flue gas temperature sensor.
X
Remove the flue ash from the chimney.
X
Check the cover and door packing cords and replace if re-
quired.
X
Check all installed position switches.
X
Maintenance of moving parts (shafts and bearings)
X
Replace the battery inside the control unit.
X
For periodic testing, please note:
■
Clean the flue gas routes and chimney 3 to 5 days
before testing. Run the boiler for at least 24 h
between cleaning and testing.
■
Heat up the boiler for approx. 1 hour before the test.
Ideally, the heating water buffer cylinder temperature
should be below 40 °C. Only half fill the combustion
chamber.
■
If the Lambda probe shows less than 20 % O
2
when
cold, clean the probe and calibrate it.
■
Observe test points:
Inlet path 2 D (2 times chimney diameter), outlet path
1- 2 D (1 to 2 times chimney diameter), extract gas
from the core flow. Test points must not be located
directly at the flue gas fan or upstream of flue bends.