54
Coding in the delivered condition
Possible change
Buffer charging until temperature
D1:75
The additional heat generator
charges the heating water buffer
cylinder until the temperature of
75 °C at the selected sensor (code
"D0:1-5"
) is reached.
D1:50
to
D1:100
Adjustable value in °C
Start delay
D2:10
Start delay of the additional heat
generator of 10 min
D2:0
to
D2:250
Adjustable value in min
Start temperature set system temperature
D3:-10
Start temperature of the additional
heat generator. Starting condition:
Actual system temperature < set
system temperature minus value
set (here: 10 K)
D3:-100
to
D3:-1
Adjustable value in K
Minimum runtime
D4:5
Minimum runtime of the additional
heat generator of 5 min
D4:0
to
D4:250
Adjustable value in min
Min pause duration
D5:5
Minimum pause duration of the ad-
ditional heat generator of 5 min
D5:0
to
D5:250
Adjustable value in min
Start without delay, Set system temp
D6:-20
Start of additional heat generator
without delay. Condition: Actual
system temperature < set system
temperature minus value set (here:
20 K)
D6:-100
to
D6:0
Adjustable value in K
Parallel operation
D7:1
Parallel operation of both heat
generators is possible.
Note
Parallel operation only possible
when the additional heat generator
has a boiler circuit pump.
D7:0
Parallel operation of both boilers is
not
possible.
Code 2
Calling up code 2
Note
■
At coding level 2, all codes are accessible, including
the codes at coding level 1.
■
Codes that are not assigned, due to the heating sys-
tem equipment level or the setting of other codes,
are not displayed.
Press the following keys:
1.
d
+
å
simultaneously for approx. 4 s.
The
"Service"
menu appears.
2.
ä
+
d
simultaneously for approx. 4 s.
"Code 2"
appears in the
"Service"
menu.
Codes
Code 1
(cont.)
5777 985 GB
Codes