Overview
The coding addresses are displayed in groups, subject
to system configuration:
■
"General"
See page 55
■
"Heating"
See page 56
■
"Boiler"
■
"DHW"
General
Coding
Coding in the delivered condition
Possible change
Fault message output delay
80:6
Minimum fault duration of 30 s be-
fore a fault message is issued.
80:0
to
80:199
Adjustable from 0 to 995 s. 1 step
≙
5 s.
Automatic summer/wintertime changeover
81:1
Automatic summer/wintertime
changeover
81:0
Manual summer/wintertime change-
over
Outside temperature time constant
90:128
Time constant for calculating the
adjusted outside temperature
21.5 h
90:0
to
90:199
Fast (low values) or slow (high val-
ues) matching of the flow tempera-
ture, subject to the set value accord-
ing to changes in outside tempera-
ture; 1 step
≙
10 min
Outside temperature offset
92:0
No outside temperature correction. 92:- 10
to
92:10
Correction of the outside tempera-
ture by the value set in °C.
Codes