Suction turbine with 3 wands
&
Suction turbine with 2 wands
&
Suction turbine agitator
Runtime of the suction turbine
Set the runtime of the suction turbine
subject to the length of the supply line
and the head.
Delivered condition: 50 s
Setting range: 20 to 70 s
Required runtime of the suction turbine
Length of the
supply line in m
Suction head in m
0
–
2.8
2.8
–
4.5
>
4.5
5
–
10
40 s
50 s
60 s
10
–
15
50 s
60 s
—
15
–
20
60 s
—
—
20
–
25
70 s
—
—
Number of grate shakings
To remove the ash, the grate in the
burner pot is shaken by a motor in
specified intervals. The number of
shakes per event can be adjusted.
Rated output
kW
9.9 and 15.0
21.0 and 25.9
Opera-
tion
Burnout
Opera-
tion
Burnout
Delivered condition
20
40
20
30
Setting range
10
–
30
15
–
60
10
–
30
15
–
60
Ventilation air/extract air damper
The runtime of a connected ventila-
tion air or extract air damper can be
adjusted at the control unit.
Delivered condition: Control OFF, run-
time in seconds 300
Setting range: 0 to 600 s
Note
The selected runtime should be twice
as long as the actual damper runtime.
Changing parameters and calling up operating . . .
(cont.)
7
Commissioning and adjustment
5692
618
GB
Summary of Contents for Vitolig 300
Page 27: ...Standard control Connection and wiring diagrams 27 Connection and wiring diagrams 5692 618 GB ...
Page 37: ...Parts list cont 37 Parts lists 5692 618 GB ...
Page 38: ...Parts list cont 38 Parts lists 5692 618 GB ...
Page 39: ...Parts list cont 39 Parts lists 5692 618 GB ...
Page 40: ...Parts list cont 40 Parts lists 5692 618 GB ...
Page 41: ...Parts list cont 41 Parts lists 5692 618 GB ...
Page 42: ...Parts list cont 42 Parts lists 5692 618 GB ...