1.
Start up the boiler and check the
combustion.
Flue gas limits
CO
2
content: 8 to 14 % by vol.
CO content
&
with 8% CO
2
: max. 200 ppm
&
with 14% CO
2
: max. 1000 ppm
Flue gas temperature: max. 200 °C
2.
Check the setting and function of
the boiler control unit.
15. Checking the draught
Check the draught inside the flue pipe
(for required draught, see specifica-
tions on page 45).