Checking the boiler water temperature sensor and the flue
gas temperature sensor
1.
Check the sensor resistance.
Boiler water temperature sensor
Resistance: NTC 5 k
Ω
Temperature
in °C
Pressure drop
in k
Ω
30
40
50
60
70
4.03
2.66
1.80
1.24
0.87
Flue gas temperature sensor
Resistance: PT 1000
Temperature
in °C
Pressure drop
in k
Ω
20
60
90
120
150
1.08
1.23
1.35
1.46
1.57
2.
Disconnect cores from the sensor,
if actual values deviate severely
from the curve, repeat sensor mea-
surements and compare with the
actual temperature (for scanning,
see operating instructions).
3.
Depending on the result, replace
the lead or the sensor.
Repairs
26
Troubleshooting
5692
618
GB