1.
In menu option "Parameter" high-
light the required sub-option with
"
V
" or "
v
" and confirm with
"select".
2.
Change the required parameter
with "+" or "
–
".
3.
Save the selected value with "yes".
The display briefly shows "Para-
meter value is being saved".
Under menu option "Parameter" you can adjust the following
parameters or call up information:
Number of burner starts
The present number of burner starts is
shown
Amount of fuel through the supply auger
The amount of fuel captured by the
combustion controller is displayed in
kg/h.
Hysteresis burner ON
Switching hysteresis for burner con-
trol.
Delivered condition: 5 K
Setting range: 0 to 20 K
Maximum value of the set temperature
Maximum set boiler water tempera-
ture in heating mode
Delivered condition: 75 °C
Setting range: 60 to 75 °C
Set temperature ext. heat demand
Set boiler water temperature in case
of external heat demand
Delivered condition: 75 °C
Setting range: 35 to 75 °C
Pellet supply
A pellet supply system must be
adjusted subject to the type of pellet
extraction from the storage room.
Delivered condition: without supply
system
Optional changes:
Changing parameters and calling up operating information
6
Commissioning and adjustment
5692
618
GB
Summary of Contents for Vitolig 300
Page 27: ...Standard control Connection and wiring diagrams 27 Connection and wiring diagrams 5692 618 GB ...
Page 37: ...Parts list cont 37 Parts lists 5692 618 GB ...
Page 38: ...Parts list cont 38 Parts lists 5692 618 GB ...
Page 39: ...Parts list cont 39 Parts lists 5692 618 GB ...
Page 40: ...Parts list cont 40 Parts lists 5692 618 GB ...
Page 41: ...Parts list cont 41 Parts lists 5692 618 GB ...
Page 42: ...Parts list cont 42 Parts lists 5692 618 GB ...