L
DHW only
G
Heating and DHW
M
Party mode
N
Economy mode
b
/
a
Setting values
d
Confirmation
c
Information
e
Standard settings (Reset)
Heating operation
The control unit determines a set boil-
er water temperature subject to out-
side temperature or room temperature
(if a room temperature-dependent
remote control is connected) and to
the slope/level of the heating curve.
The determined set boiler water tem-
perature is transferred to the burner
control unit. From the set and actual
boiler water temperatures, the burner
control unit calculates the modulation
level and regulates the burner accord-
ingly.
The electronic temperature limiter
inside the burner control unit limits the
boiler water temperature to 82 °C.
DHW heating
The burner, the circulation pump and
the three-way valve are started or
changed over, if the cylinder tempera-
ture lies 2.5 K below the set cylinder
temperature.
The set boiler water temperature is
adjusted 20 K higher than the set
DHW temperature (adjustable via
coding address "60"). The burner will
be switched OFF and the circulation
pump run-on time will begin, if the
actual cylinder temperature exceeds
the set cylinder temperature by 2.5 K.
Boosting DHW heating
The booster heating function is acti-
vated if a switching period is selected
for the fourth time phase.
The set temperature value for the
heating boost is adjustable in coding
address "58".
Weather-compensated control unit
(cont.)
91
Function description
5692
673
GB
Summary of Contents for VITODENS 300-W
Page 111: ...Parts lists cont 111 Parts lists 5692 673 GB...
Page 112: ...Parts lists cont 112 Parts lists 5692 673 GB...
Page 113: ...Parts lists cont 113 Parts lists 5692 673 GB...
Page 114: ...Parts lists cont 114 Parts lists 5692 673 GB...
Page 121: ...121 5692 673 GB...
Page 122: ...122 5692 673 GB...
Page 123: ...123 5692 673 GB...